Handling The Front Door; Detaching The Cover Of The Control Unit; Pulling Out The Compressor Module - Gebwell Aries Series Installation And Commissioning Manual

Ground source heat pump
Table of Contents

Advertisement

pump is 45°. The heat pump should not be turned onto its
side. However, if it is necessary to turn the heat pump onto
its side for reasons such as transportation, the compressor
unit can be removed during transportation. However, the
heat pump must not be transported upside down. If it is
necessary to tilt the heat pump, the heat pump must be left
in the vertical position for at least two hours before
starting up to ensure that the lubricating oil in the
compressor flows into the right place. The heat pump
should only be lifted by the pallet. The device must be
transported to the place of installation on the pallet.
4.5

Handling the front door

The heat pump front door has to be removed during
operations inside the heat pump. To remove the front door,
lift it straight up. Lifting can be assisted with a foot at the
bottom. To reinstall the door, lift the door so that the lip at
the bottom of the door goes into the slot on the bottom of
the heat pump and the lip on the top of the door sits at the
top of the heat pump.
4.6

Detaching the cover of the control unit

The cover of the control unit is attached with four hex
screws. You will need a 6-mm ring spanner or socket
wrench to open the cover.
12
4.7

Pulling out the compressor module

The compressor module can be detached from the heat
pump to facilitate transportation and servicing.
1.
Close the shut-off valves (VS1–VS4).
2.
Open the insulation from beneath the shut-off valves
so that you can open the pipe system's mounting nuts.
When you open the mounting nuts, hold on to the key
barrel for the flexible pipe underneath using the other
key.
3.
Turn the shut-off valves of the collection pipes closest
to the edge into the horizontal position (the O-ring
seals permit this without squeaking).
4.
Detach the two screws from the device frame of the
compressor module at the mounts on the front edge.
5.
Pull the compressor module out using lifting straps
intended for this purpose.
6.
Detach the pipes from the connections (valves VS1–
VS4).
Aries Installation and Commissioning manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aries 6Aries 12

Table of Contents