14.3 Troubleshooting table

No.: Failure message
Location Description
10: Outdoor temperature
B9
sensor
31: Supply water sensor
B16
refrigeration 1
32: Supply water sensor
B12
2
33: Heat pump supply
B21
water sensor
35: Source input sensor
B91
36: Hot gas sensor 1
B81
44: Heat pump return
B71
water sensor
45: Source output sensor B92
50: Domestic hot water
B3
sensor 1
60: Room temperature
sensor 1
98: Additional module 1
99: Additional module 2
102: No emergency
clock operation
105: Service notification
106: Source temp. too
low
107: Hot gas, compr. 1
No.: Failure message
Location Description
38
Reason
Fault in the outdoor
Fault in the electrical
temperature sensor or
system
sensor not connected.
Fault in the refrigeration
Fault in the electrical
supply water sensor
system
Fault in the supply water
Fault in the electrical
sensor in heating circuit
system
2
Fault in the heat pump's
Fault in the electrical
charging supply water
system
sensor
Fault in the collector
Fault in the electrical
input sensor
system
Fault in the hot gas
Fault in the electrical
sensor
system
Fault in the heat pump's
Fault in the electrical
charging return water
system
sensor
Fault in the collector
Fault in the electrical
output sensor
system
Fault in the domestic hot
Fault in the electrical
water accumulator
system
sensor
Fault in the room
Fault in the electrical
temperature sensor
system
The regulator does not
Fault in the electrical
detect expansion module
system
1 on the bus
The regulator does not
Fault in the electrical
detect expansion module
system
2 on the bus
The battery in the
Fault in the electrical
regulator's user terminal
system
is running out
A service notification
has been programmed
on the regulator
The collector's input
Flow rate too low in the
temperature is lower
collector
than the value set in the
menu. The controller
automatically restores
the situation after 4
hours.
This alert is triggered
when the hot gas sensor
shows 130°C. Three
alerts are permitted
within eight hours for
automatic restoration.
Reason
Action
Action
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary.
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary.
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary.
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary
Contact an authorised
Check that the sensor is intact and
technician
correctly connected. Contact
Gebwell maintenance if
necessary.
Contact an authorised
Check that the room temperature
technician
sensor is connected and is not
externally damaged. If necessary,
contact an authorised technician
Contact an authorised
Check that the ribbon cable
technician
between the regulators is attached.
Check that current is supplied to
the expansion module (green
light)
Contact an authorised
Check that the ribbon cable
technician
between the regulators is attached.
Check that current is supplied to
the expansion module (green
light)
Contact an authorised
Check that the display's ribbon
technician
cable is properly connected to the
regulator and the display
Contact an authorised
Perform annual servicing of the
technician
equipment
Check that the stop
Check the functionality of the
valves in the
collector.
collector are open.
Check the collector's
sanitary trap. If
necessary, contact an
authorised
technician.
Contact an authorised
Check the functionality of the
technician
refrigeration machinery
Action
Action
Aries Installation and Commissioning manual