The material in this instruction manual is for informational purposes only. • Gebwell Ltd reserves the right to change its products in order to improve their reliability, operation, design or other properties without prior notice. Gebwell Ltd is not liable for any damages, losses, costs or expenses incurred by or related to the use of this instruction manual or the products discussed therein.
The CE mark is the manufacturer’s declaration that the product conforms to EU legal requirements. Gebwell Ltd affirms that the product meets all of the requirements of relevant EU directives. The purpose of the CE mark is to facilitate the free movement of goods on the internal market in Europe.
Page 9
(such as remote access). Gebwell is not liable for the operation of mobile data or the costs incurred due to measures taken to improve mobile data functionality, such as the costs of signal boosters.
Page 10
If a fault is detected during the warranty period, the customer must immediately (normally within 14 days) report it to the Gebwell retailer that sold the product. The information to be provided includes the equipment model and serial number of the product and a detailed description of how the fault was found and the conditions under which it occurred and/or arises.
1 General You can also access the registration page on a smartphone by using the QR code below. If you are unable to register the heat pump, call Gebwell Ltd on +358 20 1230 800. Gebwell Ltd contact information Gebwell Ltd (2008956-7) Patruunapolku 5, FI-79100 Leppävirta, Finland...
After commissioning, the heat pump sends telemetry data to the Gebwell Smart cloud automatically. Data storage in the cloud enables the display of the device’s history data in the Gebwell Smart control room and system optimization. The data can also be used for maintenance and product development purposes.
During the summer, the temperature of cold collecting liquid can also be used for cooling the building in an environmentally friendly way. Further information about heat collection systems and their dimensioning can be found on the websites of Gebwell Ltd and the Finnish Heat Pump Association (SULPU). www.gebwell.fi www.sulpu.fi...
(B3) at the bottom turns the charging process on and off. The domestic water temperature is set to the heat pump’s controller via the Gebwell Smart Control Hub, application or controller. Based on the set temperature, the heat pump produces domestic water for the accumulator.
Before unloading the delivery, the recipient must inspect it for any damage. Possible damage must be recorded in the waybill and the transport company should be notified. 4.1 Delivery content • Gebwell Taurus Inverter Pro or Gebwell Taurus 80/110 EVI heat pump • Installation, commissioning and maintenance manual • Electrical diagrams •...
Make sure that the heat pump cannot tip over during transport or lifting. The WARNING Taurus Inverter Pro heat pump weighs 876 kg and Taurus 80/110 EVI heat pump weighs 700 kg. When transporting or lifting the Taurus Inverter Pro heat pump, take into account WARNING that the pump is rear-heavy.
Page 34
5 Installing the heat pump Figure 5.2 - Centre of gravity – Taurus Inverter Pro heat pump Figure 5.3 - Centre of gravity – Taurus 80/110 EVI heat pump Whenever possible, use a pallet truck or similar to transport the heat pump all the way to the installation site.
Page 39
5 Installing the heat pump Figure 5.9 - Removing the brackets In addition to these brackets, the sprung compressor base of the Taurus Inverter Pro heat pump is supported by four transport supports. Figure 5.10 - Compressor supports (Taurus Inverter Pro)
6.2 Safety valve exhaust piping The refrigerant circuit of the Taurus Inverter Pro heat pump has a safety valve that protects the device from overpressure. The safety valve opens in the event of a fire, or if the high pressure pressostat and electronic pressure monitoring malfunction.
6.6 Examples of heating systems Gebwell Taurus heat pumps can be used to realise several types of heating systems. This section provides some examples. Always make installations in accordance with the planned diagram. If the diagrams have abnormal connections, check with your Gebwell specialist to ensure the correct connection.
Figure 7.28 - Connecting the cascade system 7.24 Connecting the Modbus RTU bus Gebwell Taurus can be connected to a Modbus RTU fieldbus as a slave device. Connect the Modbus bus cable to the RS-485 connector (T6) of the heat pump controller. Set the Modbus communication settings (slave address, baud rate, parity and stop bits) in the heat pump controller.
8.4 Starting up the heat pump 1. Set the heat pump’s main switch (Q1) in the ON position. 2. Set the other switches to the ON position: ◦ Frequency converter (F1), Taurus Inverter Pro only ◦ source pump (F2) ◦...
With the Taurus Inverter Pro heat pump, the device starts when the minimum speed of the compressor is exceeded, and shuts down when the request is removed (0 %). The device rotates at a minimum speed when the request is 1 % –...
The Modbus communication link enables the device’s temperatures, status information, setpoints and malfunctions to be read by a higher-level automation system. Via the Modbus connection, Gebwell’s heat pumps can be controlled by sending a heat request in percentages (%) or a setpoint in Celsius degrees (°C).
Page 79
Modbus TCP communication takes place over the TCP/IP network using port 502. As a communications media, a standard Ethernet cable (e.g. CAT5 twin cable) is used. Master and slave devices must be within the same IP space. The IP addresses of Gebwell’s heat pumps are usually as follows: • 1st device: 192.168.1.10 •...