Carrier 80AWX Series Installation Manual page 34

Control module
Table of Contents

Advertisement

Maintenance
Error
Item
code
G-Tr short circuit
18
protection
Position
20
Detection Circuit
Error
Current Sensor
21
Error
Outdoor Heat
22
Exchange Sensor
(TE) / (TS)
Discharge
Temperature
23
Sensor
(TD)
Outdoor Fan
24
Error
Other Outdoor
26
Error
27
Compressor Lock
Discharge
28
Temperature
Error
Compressor
29
Breakdown
Other inverter
30
board error
High
31
Temperature
Release
70
Configuration
80AWX- 80AWH
34
Failure when
Inverter over-
current protective
circuit operates.
Outdoor unit stops
Short circuit
Domestic water valve OFF if code
voltage protection
127=1
of main circuit
operates
Position detection
circuit operates
when the
Outdoor unit stops
compressor is
Domestic water valve OFF if code
operating despite
127=1
removal of 3P
connector.
Current detection
circuit error:
• Current value
Outdoor unit stops
at AC side is high
Domestic water valve OFF if code
when compressor
127=1
is OFF
• Phase of power
supply is missing
Outdoor unit stops
Value out of range
Domestic water valve OFF if code
127=1
Outdoor unit stops
Value out of range
Domestic water valve OFF if code
127=1
Defective
detection of
position
Operation of
Outdoor unit stops
outdoor fan over-
Domestic water valve OFF if code
current protection
127=1
circuit
Outdoor fan
locked
Outdoor unit stops
Domestic water valve OFF if code
127=1
Defective cabling
Outdoor unit stops
of compressor
Domestic water valve OFF if code
127=1
Compressor fault
Outdoor unit stops
Error of discharge
Domestic water valve OFF if code
temperature
127=1
Abnormal
Outdoor unit stops
compressor
Domestic water valve OFF if code
operation
127=1
Outdoor unit stops
Domestic water valve OFF if code
127=1
Outdoor unit stops
Domestic water valve OFF if code
127=1
User interface fault codes
Code 104 not
equal to 242 or
Communication is disabled
243 or 244
Consequences
Diagnostics and solutions
Check Outdoor unit board for cabling
error
Replace Outdoor unit board
Check outdoor unit board.
Check 3 phase power voltage and
cables
Check sensor, wiring and electrical
connections
Check sensor, wiring and electrical
connections
Check outdoor fan
Check outdoor unit board
Check 3 phase compressor power
cables
Replace compressor
Check for refrigerant gas leaks
Check PMV operation
Check TD sensor operation
Check power supply: AC 220 V +/-10%
Overload operation of refrigerating
cycle
Check current detection circuit at
AC side
Check outdoor temperature sensor TE
in the Outdoor unit
Check Outdoor unit board
Change setting of code 104.

Hide quick links: