Carrier 80AWX Series Installation Manual page 19

Control module
Table of Contents

Advertisement

Controller operation
Code
Level
Variable Name
Nr.
SlAve Output
109 Inst.
COnfIgurAtIOn
110 Inst.
HuMIDItY lIMIt
111 Inst.
AntIfrOSt t°
HeAt ClIMAtIC
112 Inst.
nuMber
113 Inst.
regIOn t° O
114 Inst.
StOp H t° O
115 Inst.
nO HeAt t W1
116 Inst.
MAX W t° W1
117 Inst.
nO HeAt t W2
118 Inst.
MAX W t° W2
COOl ClIMAtIC
119 Inst.
nuMber
120 Inst.
MAX regIOn t°
121 Inst.
COOl StOp t°
122 Inst.
MIn COOl W t°
123 Inst.
MAX COOl W t°
124 Inst.
MIn COOl W t°
125 Inst.
MAX COOl W t°
DESCRIPTION
use Days button for the selection of below
0
0. 3 way valve
1. Others
1
0. zone 1: fan coils do not work when Domestic hot water
valve is activated
1. zone 1: fan coils always working
2. zone 1: fan coils do not work when Domestic hot water
valve is activated, unless the mode is Cool
3. zone 1: Dehumidifier
2
0. zone 2: fan coils do not work when Domestic hot
water valve is activated
1. zone 2: fan coils always working
2. zone 2: fan coils do not work when Domestic hot
water valve is activated, unless the mode is Cool
3. zone 2: Dehumidifier
this code defines the Humidity threshold limit to enable the
output for the external de-humidifier
this code is defining the temperature below which the
water frost protection will be activated
Climatic Curve
use Days button for the selection of Heat climatic curve:
0. - zone 1
0. no predefined climatic curve(Installer has to set climatic
curve)
1 - 6. See manual for climatic curve details
1. - zone 2
0. no predefined Climatic Curve (Installer has to set
climatic curve)
1 - 6. See manual for climatic curve details
Minimum outdoor t° depending on the country where the
system is installed (Heat Climatic Curve Zone 1 and 2)
If outdoor t° is equal or greater then the value of this code,
minimum water tempreature is considered (Heat Climatic
Curve Zone 1 and 2)
In Heat mode, minimum water t° going to terminal zone 1
(Heat Climatic Curve Zone 1)
In Heat mode, maximum water t° in terminal zone 1 (Heat
Climatic Curve Zone 1)
In Heat mode, minimum water t° going to terminal zone 2
(Heat Climatic Curve Zone 2)
In Heat mode, maximum water t° in terminal zone 2 (Heat
Climatic Curve Zone 2)
Days button shall be used for the Selection of Cool climatic
curve:
0. - zone 1
0. no predefined climatic curve(Installer has to draw
climatic curve)
1 - 2. See manual for climatic curve details
1. - zone 2
0. no predefined climatic curve (Installer has to draw
climatic curve)
1 - 2. See manual for climatic curve details
Maximum outdoor t° depending on the Country where the
system is installed (Cool climatic Curve Zone 1 and 2)
If outdoor t° is equal or less then the value of this code,
maximum water tempreature is considered (Cool Climatic
Curve Zone 1 and 2)
In Cool mode, minimum water t° going to terminal zone 1
(Cool climatic Curve zone 1)
In Cool mode, maximum water t° going to terminal zone 1
(Cool climatic Curve zone 1)
In Cool mode, minimum water t° going to terminal zone 2
(Cool climatic Curve zone 2)
In Cool mode, maximum water t° going to terminal zone 2
(Cool climatic Curve zone 2)
VALUE RANGE
DEFAULT
Min
Max
1
3
0
3
3
20
100
100
4°C
10
4°C
0
6
0
-20°C
10 °C
-7°C
15°C
50°C
20°C
20°C
60°C
20°C
20°C
80°C
35°C
20°C
60°C
40°C
20°C
80°C
55°C
0
2
0
30°C
50°C
40°C
0°C
25°C
22°C
4°C
20°C
12°C
4°C
20°C
18°C
4°C
20°C
6°C
4°C
20°C
12°C
80AWX- 80AWH
19