Carrier 80AWX Series Installation Manual page 18

Control module
Table of Contents

Advertisement

Controller operation
Code
Level
Variable Name
Nr.
106 Inst.
INTERFACE CONFIG
FLOW SWITCH
107 Inst.
CONFIGURATION
MASTER OUTPUT
108 Inst.
CONFIGURATION
80AWX- 80AWH
18
DESCRIPTION
Use Days button and do the selection of below
0. Domestic hot water input - configuration
0: contact close: input is active / contact open: input is
not active
1: contact close: input is not active / contact open: input
is active
1. Space heat/cool ON/OFF input - configuration (no impact
on Domestic Hot Water production)
0: contact close: unit produces space htg/clg / contact
open: unit does not produce space htg/clg
1: contact close: unit does not produce space htg/clg /
contact open: unit produces space htg/clg
2. Heat / Cool selection input- configuration
0: contact close: unit performs space heating / contact
open: unit performs space cooling
1: contact close: unit performs space cooling / contact
open: unit performs space heating
3. Hi energy rate input - configuration
0: contact close: high energy rate / contact open:
normal energy rate
1: contact close: normal energy rate / contact open:
high energy rate
4. External HTG/CLG
0: Mode (Heat/Cool) is determined by dry contact
1: Mode (Heat/Cool/OFF/Domestic Hot Water) is
determined by user interface (106.2 is ignored)
5. Cool Z1
0: Cool in Zone 1 forbidden
1: Cool in Zone 1 permitted
6. Cool Z2
0: Cool in Zone 2 forbidden
1: Cool in Zone 2 permitted
7. System ON / OFF input - configuration
0: contact close: system OFF / contact open: system
running
1: contact close: system running / contact open:
system OFF
Use Days button and do the selection of below
0.
0: Open - flowing / Short: not flowing
1: Short - flowing / Open: not flowing
1.
0: Do not allow water flowing when unit pump is OFF (no
external pump used)
1: Allow water flowing when unit pump is OFF (external
pump used)
Use UP/Down buttons for choosing 1 to 10.
1. Fan Coil - Fan coils do not work when Domestic hot water
valve is activated
2. Fan Coil - Fan coils always working
3. Fan coils do not work when Domestic hot water valve is
activated, unless the mode is Cool
4. Dehumidifier
5. All alarms
6. Alarms stopping the outdoor unit
7. Alarms stopping the entire system
9. Defrost
10. All alarms + Defrost
11. Alarms stopping the outdoor unit + Defrost
12. Alarms stopping the entire system + Defrost
13. Not used
14. Not used
15. Not used
16. Not used
VALUE RANGE
DEFAULT
Min
Max
0
1
1
0
0
1
1
0
0
0
1
0
1
0
1
16
4