Venting - State Water Heaters Utra-Force STC-077 Service Handbook

Commercial gas water heaters with 94% thermal efficiency and electronic control system
Table of Contents

Advertisement

NUMBER OF 90°
ELBOWS
ONE (1)
TWO (2)
THREE (3)
FOUR (4)
FIVE (5)
SIX (6)
4-inch PVC may be used for a MAXIMUM intake of ONE HUNDRED TWENTY (120) EQUIVALENT
FEET and a MAXIMUM exhaust of ONE HUNDRED TWENTY (120) EQUIVALENT FEET. The
maximum number of 90° elbows with the 4-inch venting is six (6) on the intake and six (6) on the
exhaust. A 90° elbow is equal to five (5) equivalent feet of pipe. One (1) 90° elbow is equal to two
(2) 45° elbows. Any venting configuration using less than 50 equivalent feet should use 3-inch vent-
ing. See Vent Length Table.
The 3-inch venting terminals (provided) must be used with the 4-inch venting by adding 4 x 3
reducing coupling at the venting terminals. A reducing coupling is also needed immediately after
the condensate elbow (exhaust) and immediately before the 3-inch blower adapter (intake) if direct
venting is installed. See Vent Length Table.
The air intake provided on the unit contains a mesh screen (see Figure below) to prevent large par-
ticles from entering the unit.
3" (7.6CM) 45° PVC ELBOW WITH MESH SCREEN
Technical Training Department
STC-077
S U F
S E R V I C E
I N S T A L L A T I O N

VENTING

Equivalent Feet of Pipe Intake or Exhaust
VENT LENGTH TABLE
3" MINIMUM
PIPE (FEET)
7
7
7
7
7
7
DIRECT VENTING
H A N D B O O K
3" MAXIMUM
PIPE (FEET)
45
40
35
30
--
--
WARNING WHEN THE UNIT IS TO
BE SETUP AS A DIRECT VENT, THE
MESH SCREEN MUST BE REMOVED.
THE INLET VENT PIPE MAY THEN BE
GLUED TO THE AIR INTAKE (see follow-
ing Figure) PROVIDED ON THE UNIT.
4
4" MAXIMUM
PIPE (FEET)
115
110
105
100
95
90
State Water Heaters
Ashland City, Tennessee © 2004