fault and alert MessaGes (cont)
Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent in
your area.
possIble causes - checK/repaIr
•
The control system has detected the Blower Prover Switch
contacts are closed when they should be open at the beginning of
a heating cycle.
•
Pinched/shorted Blower Prover Switch wiring.
•
Jumper wire connected to the Blower Prover Switch - remove
jumper wire. Jumper wires must never be used, read all Warnings.
•
Excessive wind outdoors pressurizing the vent system piping.
•
Excessive negative air pressure in the installed space.
•
The control system has detected the Blower Prover Switch
contacts are remaining open after the control system has
energized the Combustion Blower.
•
Loose or open wiring to the Blower Prover Switch.
•
Blower Prover Switch air sensing tube disconnected, kinked, filed
with condensate, damaged or leaking - repair or replace tube.
•
Combustion Blower is not running when energized.
•
Loose or open wiring to Combustion Blower.
•
The control system has detected the Blocked Intake Air Switch
contacts are open.
•
Loose or open wiring to the Blocked Intake Air Switch.
•
Excessive equivalent pipe length, exceeded the maximum number
of 90° elbows or wrong pipe size used in the intake air piping
system.
•
Excessive negative air pressure in the installed space.
•
The control system has detected the ECO (energy cut out) Switch
contacts are open.
•
The ECO switch is a normally closed switch that opens on a
temperature rise to prevent excessive water temperature in the
storage tank. The ECO switch is inside the Temperature Probe
(two red wires).
•
Loose or open wiring to the ECO switch in the Temperature Probe
- two red wires.
dIsplaYed fault/alert MessaGe
Blower Prover Failure
The blower prover switch is
closed out of sequence.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
CHANGE
Blower Prover Open
The blower prover switch remains
open after the blower has been
energized.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
CHANGE
Blocked Air Intake
The combustion air intake is
restricted.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
CHANGE
Energy Cut Out (ECO)
Tank temperature is excessive.
The water heater has been
disabled.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
CHANGE
55
Fault occurred 2 mins ago
BACK
ADVANCED
Fault occurred 2 mins ago
BACK
ADVANCED
Fault occurred 2 mins ago
ADVANCED
BACK
Fault occurred 2 mins ago
BACK
ADVANCED