Applications

5.2 Controlling and Silencing Four NACs

In this application, the power supply has been set as a master with synchronized, silenceable outputs (see SW1 switch settings in follow-
ing illustration). The four NAC (Notification Appliance Circuits) output circuits can be silenced in the sync generation mode by remov-
ing alarm input from Signal Input 2. This can be accomplished using two addressable modules as illustrated in Figure 5.2.
The FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the HPFF unit(s) are con-
nected. The addressable modules are shown to demonstrate the use of a remotely mounted device associated with an addressable fire
alarm control panel. The module could be replaced with any circuit capable of polarity reversal, such as an FACP NAC.
Two independent inputs are required for silencing. Two separate addressable modules can be used as shown in Figure 5.2, mounted on
the control board (one on the other) or in a separate UL-Listed panel. Alternately, two outputs of a six-output addressable module can
also be used and mounted on the Control board (see Section 5.3, "Split Alarm and Selective Silence").
SW1-8
OFF
All four NAC outputs will have silenceable sync for System Sensor devices.
TB2
LEDs
J1
TB1
TB4
BATT+ BATT–
Notes for Figure 5.2:
1.
When the power supply is in normal/standby state, a trouble will result in an open circuit condition on the control module output
circuit (monitored by the End-of-Line Resistor on TB3). The HPFF's alarm input circuit will always remain closed in the alarm
state. Therefore, the Trouble contacts at TB2 need to be used to report troubles to the FACP during an alarm. Section 4.1,
"Supervised Functions and Field Wiring".
2.
The addressable relay module must be programmed as a silenceable point at the FACP to allow silencing of horn/strobe devices.
3.
The addressable control module must be programmed as a non-silenceable point at the FACP.
4.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
5.
The value of the ELR (End-of-Line Resistor) across TB3 terminals depends on the control module used.
6.
For a list of compatible devices, refer to the HPP Device Compatibility Document.
7.
The same gauge wire must be used if two conductors are connected to the same terminal of any terminal block.
8.
Do not complete a continuous circuit around the screw terminal. There must be two separate wires on either side of the screw at the
terminal block. "T-tapping" is absolutely NOT ALLOWED.
36
SW1-7
SW1-6
NA
OFF
Out #1 +
Out #1 -
Out #2 +
Out #2 -
A+
A–
1L1
1L2
2L1
2L2
3L1
3L2
4L1
Figure 5.2 Controlling and Silencing Four NACs
SW1-5
SW1-4
ON
ON
Pwr-
SW2
Pwr+
TB3
Ref +
Ref -
In #1 +
In #1 -
In #2 +
In #2 -
J2
4L2
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
Controlling and Silencing Four NACs
SW1-3
SW1-2
SW1-1
OFF
ON
OFF
SLC
A/B-
A/B+
Control Module
Non-Silenceable Point
Activated by Alarm
Supervision
Relay
ELR
SLC
Relay Module
Silenceable Point
Activated by Alarm
Alarm Polarity
Shown

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpff12eHpff12cmeHpff12cm

Table of Contents