Split Alarm And Selective Silence; 1: Selective Silence - Honeywell HPFF12 Instruction Manual

Notification appliance circuit expander
Hide thumbs Also See for HPFF12:
Table of Contents

Advertisement

Split Alarm and Selective Silence

5.3 Split Alarm and Selective Silence
Selective silence can only be accomplished if the sync protocol from the FACP is passed through the HPFF unit, which is configured for
Split Alarm. The selective silencing is accomplished in pairs of NACs 1&2 and 3&4.
5.3.1 Selective Silence
In this application, the power supply and FACP have been configured for selective silence as illustrated in Figure 5.3. The sync protocol
has to be passed through the HPFF unit from the FACP to selectively silence the NACs. The FACP must be capable of a visual annunci-
ation to the silencing status of the output or zone(s) to which the HPFF unit(s) are connected.
If the Programming DIP Switches are set as shown below, all four NACs will follow (Pass-through) the signal from the FACP including
which NAC output pair will be silenced.
SW1-8
ON
NAC 1 & 2 will NOT be silenced; NAC 3 & 4 will be silenced.
Two independent inputs are required for silencing. Two separate addressable modules can be used as shown in Figure 5.2, mounted on
the control board (one on the other) or in a separate UL-Listed panel. Alternately, two outputs of a six-output addressable module can
also be used and mounted on the Control board as shown in Figure 5.4.
TB2
LEDs
J1
TB1
TB4
BATT+ BATT–
Notes for Figure 5.3:
1.
When the power supply is in normal/standby state, a trouble will result in an open circuit condition on the control module output
circuit (monitored by the End-of-Line Resistors on TB3). The HPFF's alarm circuit will always remain closed in the alarm state.
Therefore, the Trouble contacts at TB2 need to be used to report troubles to the FACP during an alarm. See Section 4.1, "Supervised
Functions and Field Wiring".
2.
The FACP NAC outputs must be programmed as a silenceable points and the HPFF12 programmed for Selective/Split Alarm to
allow selective silence of horn/strobe devices.
3.
The value of the ELRs (End-of-Line Resistors) on TB3 depends on the FACP used.
4.
For a list of compatible devices, refer to the HPP Device Compatibility Document.
5.
The same gauge wire must be used if two conductors are connected to the same terminal of any terminal block.
6.
Do not complete a continuous circuit around the screw terminal. There must be two separate wires on either side of the screw at the
terminal block. "T-tapping" is absolutely NOT ALLOWED.
HPFF12 NAC Expander — P/N 53576:B3 10/1/2018
SW1-7
SW1-6
NA
OFF
In #1 +
Out #1 +
Out #1 -
In #2 +
Out #2 +
Out #2 -
A+
A–
1L1
1L2
2L1
2L2
3L1
3L2
4L1
Figure 5.3 Wiring for Selective Silence
SW1-5
SW1-4
OFF
OFF
SW2
TB3
Ref +
Ref
Ref -
+
Class B NAC output from FACP or Sync Module:
Non-Silenceable Point Activated by Alarm
-
In #1 -
ELR
+
Class B NAC output from FACP or Sync Module:
Silenceable Point Activated by Alarm
-
In #2 -
ELR
J2
4L2
SW1-3
SW1-2
SW1-1
OFF
OFF
ON
Alarm Polarity
Shown
Applications
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpff12eHpff12cmeHpff12cm

Table of Contents