■ Parameters
• In each level, if you press the mode key on the final parameter, you will return to the parameter at the top of the level.
Advanced function setting level
init
Parameter initialization
off
l.
Select the number of
en-m
multi-SP used, with 2
1
or 4 as the designated
l.
value
Event input assignment 1
none
l.
Event input assignment 2
stop
l.
ospu
Multi-SP uses
off
on off
l.
Standby sequence reset
rest
method
Conditions for resetting
a
following the cancellation of
l.
a standby sequence
Alarm 1 open in alarm
al1n
n-o
l.
C
alh1
Alarm 1 hysteresis
0 2
l.
Alarm 2 open in alarm
al2n
n-o
l.
C
alh2
Alarm 2 hysteresis
0 2
l.
α
alfa
2 PID parameters
0.65
l.
Input digital filter
inf
Set the time constant,
0 0
with a unit of s
l.
Additional process value display
First display off in operation level
off
l.
Automatic return of display mode
ret
Pressing a key on the operation
panel automatically returns to
off
l.
operation level
a 1lt
off
l.
a2lt
off
l.
Multi-value
setting and
prlt
stop/run input
3
l.
sero
off
l.
cjc
on
l.
off
l.
a 1on
0
SP alarm output 1
l.
activation status
a2on
0
l.
a 1of
0
SP alarm output 2
l.
activation status
a2of
0
l.
off
l.
C
p-db
0
l.
on
l.
oanl
on
l.
Digital Position-Proportional Controllers
Alarm 1 latch
Activate
alarm latch
Alarm 2 latch
Move to protect level time
Input error output
Cold junction
compensation method
MB command logic switching
Alarm 1
ON delay
Alarm 2
ON delay
Setting the
alarm output's
Alarm 1
ON delay/ OFF
OFF delay
delay
Alarm 2
OFF delay
Additional MV
for stop/error
Process value dead band
Valve opening display
Manual MV
Limits in effect
Initial setting level
in-t
Input type
5
l.ini
in-h
Scaling upper limit
100
l.ini
in-l
Scaling lower limit
Only used in analog
0
input settings
l.ini
dp
Decimal point
0
l.ini
d-u
Temperature unit ˚C / ˚F
c
is Celsius, and
is Fahrenheit
l.ini
C
sl-h
SP upper limit
1300
l.ini
Limit the set point
C
sl-l
SP lower limit
-200
l.ini
Direct / reverse operation
Direct operation: on-d
Reverse operation: or-r
l.ini
alt1
Alarm 1
2
l.ini
Select alarm mode
alt2
Alarm 2
2
l.ini
Closed / floating
clfl
Floating: flot
flot
Closed: clos
l.ini
Electro-mechanical calibration
calb
Electro-mechanical calibration: on
off
Cancel: off
l.ini
mot
Travel time
30
l.ini
Switch to advanced function setting level
To switch to the advanced function
setting level, the initial setting/
0
communications protection parameters
must be set to 0.
E5EZ-PRR
43