REPAIR
The only repair recommended for the LP916 is the
replacement of the plate and tube assembly, gaskets,
restriction plate, and filters with connector assembly and
gasket. Since February 1984, models have a different
connector assembly with a single gasket, these are included
in Repair Kit 14003113-002, as shown in Figure 8. All
available parts are listed in the PARTS AND ACCESSORIES
section.
EQUIPMENT REQUIRED
Gulmite Head Screw Wrench 316744-00021.
14003113-002 REPAIR KIT INSTALLATION
Turn off system air and remove LP916 from system.
Remove and save the three No. 8-32 x 7/16-in. pan
head screws from the connector assembly (Fig. 8) or
plate and tube assembly (Fig. 9 or 10).
Lift off the connector assembly and gasket or plate and
tube assembly, restriction gasket, restriction plate, body
gasket, and two filters and discard.
Place new gasket on body and align screw holes.
Position the new connector assembly on gasket and
align screw holes. A 0.007 in. restriction may be used
for models with a 0.005 in. restriction with no effect on
operation except a slightly higher air consumption. If air
consumption is a problem, connector assembly with a
0.005 in. restriction may be ordered and substituted.
Insert and tighten the three screws.
Make operational check (See OPERATIONAL CHECK).
NOTE: For 14003113-001 Repair Kit follow directions on
package.
LP916A-C PNEUMATIC REMOTE BULB THERMOSTATS
CONNECTOR
ASSEMBLY
INDICATES 0.005 IN. RESTRICTION
INDICATES 0.007 IN. RESTRICTION
Fig. 8. Repair kit 14003113-002 (0.007 in. restriction
included in kit).
7
GASKET
C8362
75-5559