York PHG6A24 Technical Manual page 8

Single package, heat pump, gas heat, 16 seer - r-410a, 208/230v - 1 phase 2 thru 5 nominal tons, 50 thru 125 mbh heat input
Hide thumbs Also See for PHG6A24:
Table of Contents

Advertisement

5331896-YTG-C-1017
PHYSICAL DATA (Continued)
NOMINAL TONNAGE:
COMPONENT
Direct Drive Indoor Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filters
Filter Size
Quantity - Size
8
MODELS:
PHG6A24
2.0
11 x 8
Centrifugal
1/3
1/2
1200 Max
48
A
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable
filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x10 (2 each), B=20x10 (3 each).
PHG6A30
PHG6B36
2.5
3.0
11 x 8
11 x 10
Centrifugal
Centrifugal
1/3
1/2
1/2
3/4
1200 Max
1200 Max
48
48
A
B
PHG6B42
PHG6B48
3.5
4.0
11 x 10
11 x 10
Centrifugal
Centrifugal
3/4
3/4
1200 Max
1200 Max
48
48
B
B
Johnson Controls Unitary Products
PHG6B60
5.0
11 x 10
Centrifugal
1
1200 Max
48
B

Hide quick links: