York MH Technical Manual

York MH Technical Manual

Add - on coils for use with split-system cooling & heat pumps

Advertisement

Quick Links

TECHNICAL GUIDE
ADD - ON COILS
FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS
MODELS: MC, PC, FC, HD, HC, UC, MH
600 - 2000 CFM
1.5 - 5 TON COILS
HORIZONTAL
DUCT
HD
UPFLOW
UNCASED
UPFLOW/DOWNFLOW
UC
UNCASED
HORIZONTAL CASED
HC
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.ariprimenet.org.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
FULL CASED
MULTI-POSITION
MC
UPFLOW
PARTIAL CASED
PC
MH
UPFLOW/DOWNFLOW
FULL CASED
FC
DESCRIPTION
R
These cooling and heat pump coils are designed to be installed with
UPG furnaces and to be matched with UPG cooling and heat pump
outdoor units. All UPG coils utilize a TXV to provide our customers
with the optimum performance and refrigerant control required for
13+ SEER systems. Coils can be ordered with a R22 TXV factory
installed that can be easily converted to R410A by changing the bolt-
on TXV.
"Flex-coils" are also available without a factory installed metering
device. For added application flexibility a R22 or R410A TXV is
installed, on "Flex-coils", in the field to meet your refrigerant choice.
Upflow/Downflow Coils Full Cased and Partial Cased
Coils –
Designed for high-efficiency to match any system, full cased
in the upflow or downflow and the partial cased in the upflow only
.
application
Multi-Position Coils -
upflow/downflow coil but with the added flexibility that allows it to be
installed any position, upflow, downflow, horizontal right or left. This
coil can be easily applied to our furnace and modular air handler in
any configuration.
Horizontal Duct Coils -
dedicated horizontal, slab coil, applications. Field transition may be
.
required
Dedicated Horizontal Cased Coils –
only or heat pump approved for horizontal furnace or modular air
handler applications. Unlike the horizontal duct coils these cased
coils match the dimensions of the furnace or modular blower
FEATURES
Thermal Expansion Valve -
coil to R22 or R410A refrigerant. A true bolt-on TXV, valve assembly
and equalizer tube are bolt-on, no brazing required. TXV and sens-
ing bulb are mounted inside the cased coil cabinet. (Must be field
supplied for all "Flex-coils")
MicroBlue™ Coated Fins -
MicroBlue™ Hydrophilic coating to enhance the removal of conden-
sate during the refrigeration cycle and reduce the possibility of water
blow-off. The MicroBlue™ coating also reduces the growth of germ
causing microbes.
Insulated Cabinet -
lated with foil faced insulation to prevent sweatin
fiberglass turfskin insulation.
Internally Clean -
dehydrated, sealed and shipped with a holding charge. The suction
and liquid lines are sealed with rubber plugs, no cutting of connection
stubs to attach line set
Durable Finish Inside and Out -
painted steel. The pre-treated flat galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep. All inter-
nal metal parts are made of G90 pre-painted steel i.e. triangular
plates, top plates, horizontal supports etc. (Coil header plates are
non-painted due to the brazing process during production.)
Optimum Heat Transfer -
nology, staggered rows of copper tubes are mechanically expanded
into aluminum fins to provide optimum air to surface contact for
ample moisture removal as well as high performance ratings.
ACCESSORIES
Refer to Price Manual for specific model numbers
TXV Kits -
Thermal expansion valve kits are available for "Flex-coil"
applications and converting R22 to R410A refrigerant or as a service
replacement. All TXV kits are non-braze
including the valve assembly and equalizer tube. (No orifice or any
other metering device is to be used in conjunction with the TXV).
Coil Casing Without Coil –
width that can be installed with the furnace or modular air handler
during initial installation. This option is available to allow the installer
the flexibility to install the coil at a later date without duct modifica-
tions.
331471-YTG-A-0507
Designed for high-efficiency like the
Available for both cooling and heat pump
These coils are cooling
Provides flexibility to convert any
All coils are treated with a
Evaporator coil cabinets are thermally insu-
g.
All evaporator coils are factory leak-tested,
.
Coil casings are made of pre-
Using the latest in heat transfer tech-
.
,
all connections are bolt-on
Coil casings are available in each
.
HD coils use

Advertisement

loading
Need help?

Need help?

Do you have a question about the MH and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for York MH

  • Page 1 Certified Quality Management System Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com for the most up-to-date technical information. Additional rating information can be found at www.ariprimenet.org. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE...
  • Page 2 331471-YTG-A-0507 COOLING CAPACITY - Coil Only Rated Model FC18A PC18A FC18B PC18B FC24A PC24A FC24B PC24B FC30A PC30A 1025 FC30B PC30B FC35B PC35B 1200 FC35C PC35C FC36A 1150 PC36A FC36B PC36B 1250 FC36C PC36C FC42B PC42B 1400 FC42C PC42C FC43C 1400 PC43C FC48C...
  • Page 3 COOLING CAPACITY - COIL ONLY Model Coil Rated CFM MC18A MC18B MC24A MC24B MC30A 1025 MC30B MC35B 1200 MC35C MC36A 1150 MC36B 1250 MC36C 1250 MC42B 1400 MC42C MC43C 1400 MC48C 1650 MC48D MC60D 1825 MC61D 2000 MC62C 1800 MC62D 2000 * See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity.
  • Page 4: Application Limitations

    331471-YTG-A-0507 COOLING CAPACITY - Coil Only RATED MODEL HD24S**H1 HD36S**H1 1192 HD48S**H1 1610 HD60S**H1 2100 * See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity. COOLING CAPACITY - COIL ONLY Rated Entering Air °F Model (Wet Bulb) HC18A...
  • Page 5 COOLING CAPACITY - COIL ONLY Model Coil Rated CFM Entering Air °F (Wet Bulb) UC18A UC18B UC24A UC24B UC30A 1000 UC30B UC36A 1150 UC36B 1200 UC36C UC42B 1400 UC42C UC48C 1600 UC48D UC60C 1800 UC60D * See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity. COOLING CAPACITY - COIL ONLY Model Coil Rated CFM...
  • Page 6 331471-YTG-A-0507 STATIC PRESSURE VS. AIRFLOW (BASED ON WET COIL) UPFLOW CASED "A" TYPE Model Airflow FC18A PC18A 1000 FC18B PC18B 1000 FC24A PC24A 1000 FC24B PC24B 1000 FC30A 1000 PC30A 1200 FC30B 1000 PC30B 1200 FC35B 1000 PC35B 1200 FC35C 1000 PC35C 1200...
  • Page 7 CASED "A" TYPE MULTI-POSITION Model Airflow MC18A 1000 MC18B 1000 MC24A 1000 MC24B 1000 MC30A 1000 MC30B 1000 MC35B 1000 MC35C 1000 MC36A 1000 1200 MC36B 1000 1200 1000 MC36C 1200 1400 1200 MC42B 1400 1600 1200 1400 MC42C 1600 1800 1200 1400...
  • Page 8 331471-YTG-A-0507 PHYSICAL DATA CASED (FC) UPFLOW/DOWNFLOW AND PARTIAL CASED (PC) UPFLOW “A” TYPE Refrig. Model Application Conn. Types FC18A3XN1 PC18A3XN1 FC18A2AN1 PC18A2AN1 Cooling/Heat Sweat FC18B3XN1 Pump PC18B3XN1 FC18B2AN1 PC18B2AN1 FC24A3XN1 PC24A3XN1 FC24A2AN1 PC24A2AN1 Cooling/Heat Sweat FC24B3XN1 Pump PC24B3XN1 FC24B2AN1 PC24B2AN1 FC30A3XN1 PC30A3XN1 FC30A2AN1...
  • Page 9 CASED (FC) UPFLOW/DOWNFLOW AND PARTIAL CASED (PC) UPFLOW “A” TYPE (Continued) Refrig. Model Application Conn. Types FC60C3XN1 PC60C3XN1 FC60C2CN1 PC60C2CN1 Cooling/Heat Sweat Pump FC60D3XN1 PC60D3XN1 FC60D2CN1 PC60D2CN1 FC62C3XN1 Cooling/Heat Sweat FC62C2CN1 Pump FC62D3XN1 Cooling/Heat Sweat Pump FC62D2CN1 HORIZONTAL - DUCT TYPE Refrig.
  • Page 10 331471-YTG-A-0507 FULL CASED “A” TYPE MULTI-POSITION Refrig. Model Application Conn. Types MC18A3XH1 MC18A2AH1 Cooling / Sweat Heat Pump MC18B3XH1 MC18B2AH1 MC24A3XH1 MC24A2AH1 Cooling / Sweat Heat Pump MC24B3XH1 MC24B2AH1 MC30A3XH1 MC30A2AH1 Cooling / Sweat Heat Pump MC30B3XH1 MC30B2AH1 MC35B3XH2 MC35B2AH1 Cooling / Sweat Heat Pump...
  • Page 11: Dimensions - Mc Coils

    (3X) = Models require field installed TXV. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. † Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. Unitary Products Group 3/4”...
  • Page 12: Dimensions - Fc Coils

    (3X) = Models require field installed TXV. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. † Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. 3/4” Flange 22”...
  • Page 13: Dimensions - Pc Coils

    (3X) = Models require field installed TXV. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. † Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details. Unitary Products Group (Opening) 22”...
  • Page 14 331471-YTG-A-0507 COIL - UC DIMENSIONS - UC Coils Dimensions — Inches Model UC18A3XN1 UC18A2AN1 UC18B3XN1 16.5 UC18B2AN1 UC24A3XN1 UC24A2AN1 UC24B3XN1 20.5 UC24B2AN1 19.875 UC30A3XN1 UC30A2AN1 UC30B3XN1 20.5 UC30B2AN1 UC36A3XN1 23.5 UC36A2AN1 UC36B3XN1 22.5 UC36B2AN1 (3X) = Models require field installed TXV. 21-1/2 19-1/2 25-1/2...