Note:

Remote Alarm Contacts

Change State with Loss
of Power
Remote Alarm
Contacts
Normally
Open
Common

Normally Closed

Contact is Closed
when SPD is Powered
and Functional
[ Normal State ]
Wire Range
#24 to #14 AWG
3X Torque
Specification
4.5 in-lbs
[ 0.5Nm ]
Wire Range
#8 to #1/0 AWG
Lug Torque
Specification
50 in-lbs
[ 5.6 Nm ]
Wire Range
#8 to #1/0 AWG
Wire Strip Length
0.5" [ 13 mm ]
Remote Alarm
Contacts
NC Contact Closed
with SPD powered
and Functional
[ Normal State ]
NC C NO
4X Wire Strip Lengths
for Phase & Neutral
Connections
0.5" [ 13 mm ]
4X Torque Specification
50 in-lbs [ 5.6 Nm ]
Remote Alarm
Contacts
NO Contact Open
with Power OFF
or SPD Requires
Replacement
NC C NO