Ac protector
Table of Contents

Advertisement

Note:
Remote Alarm Contacts
Change State with Loss
of Power
Remote Alarm Contacts
Normally Open
Common
Normally Closed
Contact is Closed
when SPD is
Powered and Functional
Torque
50 in-lbs [ 5.6 Nm ]
Wire Range
#8 to #1/0 AWG
Ground
Lug
Strip
Length
0.5" [ 13 mm ]
Wire Range
3X Torque
#10 to #4 AWG
Specification
4.5 in-lbs
[ 0.5 Nm ]
Wire Range
Wire Strip
Length
Neutral
Block
Remote Alarm
Contacts
NC
NC C NO
Wire Range
Remote Alarm
Contacts
NO
Replacement
NC C NO
3X Wire Strip Lengths
for Phase Connections
into the Disconnect
Switch
0.5" [ 13 mm ]
3X Torque Specification
for Disconnect Switch
25 in-lbs [ 2.8 Nm ]