English (GB) Installation and operating instructions Original installation and operating instructions 11.5 Performance curves, ALPHAx XX-60 (N) 11.6 Performance curves, ALPHAx 25-40 A CONTENTS 11.7 Performance curves, ALPHAx 25-60 A 11.8 Performance curves, ALPHAx XX-80 (N) These installation and operating instructions describe ALPHAx. Accessories Sections 1-6 give the information necessary to be able to unpack, 12.1 Unions and valve kits...
1.2 Symbols used in this document 1.3 Other important notes 1.2.1 Warnings against hazards involving risk of death or personal injury A blue or grey circle with a white graphical symbol indicates that an action must be taken. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious personal injury.
3. Installing the product The arrows on the pump housing indicate the flow direction through the pump. See fig. 1, pos. A. 3.1 Mechanical installation See section 10.2 Dimensions, ALPHAx XX-40, XX-50, XX-60, or section XX-80 10.3 Dimensions, ALPHAx 25-40 A, 25-60 1.
3.2.2 Positioning the control box in air-conditioning and CAUTION cold-water systems Hot surface Position the control box with the plug pointing downwards. See Minor or moderate personal injury. fig. 4. - Position the pump so that persons cannot accidentally come into contact with hot surfaces. CAUTION Pressurised system Minor or moderate personal injury.
3.4 Insulating the pump housing 4. Electrical installation Fig. 9 Electrical connection DANGER Electric shock Death or serious personal injury - Switch off the power supply before starting any work on the product. Make sure that the power supply cannot be accidentally switched on. DANGER Electric shock Fig.
4.1 Assembling the plug Step Action Illustration Step Action Illustration Max. 1.5 mm Screw the cable gland onto the 12 mm Fit the cable gland power supply and plug cover to plug. the cable. Strip the cable 7 mm conductors as illustrated.
4.2 Disassembling the plug 4.3 Electrical installation, ALPHA SOLAR Step Action Illustration Loosen the cable gland and remove it from the plug. PWM = Power = Fig. 11 Control box connections Pull off the plug cover while 4.4 Power supply connection, ALPHA SOLAR pressing on both Connect the pump to the power supply with the TE Superseal sides.
5. Starting up the product 5.3 Venting the heating system 5.1 Before startup Do not start the pump until the system has been filled with liquid and vented. Make sure that the required minimum inlet pressure is available at the pump inlet. See sections 3.
6. Product introduction 6.1 Product description Max. 95 %RH Fig. 15 Model type on the packaging IPX4D Min./Max. ° ° +2 C / +110 Max. 1.0 MPa (10 bar) Min./Max. ° ° 0 C / +40 Fig. 16 Model type on the nameplate <...
6.3 Pumped liquids 6.4 Identification For more information about the pumped liquids, warnings and 6.4.1 Nameplate operating conditions, see fig. 14. In heating systems, the water must meet the requirements of accepted standards on water quality in heating systems, for example the German standard VDI 2035.
Page 12
The table below shows the ALPHAx models with built-in functions. Model B Model C Model D ALPHA3 model A Functions/features 2012 2015 2015 2015 AUTO ● ● ● ● ADAPT Proportional pressure ● ● ● ● Constant pressure ● ● ●...
7.6 Button for selection of pump setting Every time you press the button , the pump setting is changed. See fig. 18, pos. 5. A cycle is ten button presses. See section 7.3 Light fields indicating the pump setting. 7.7 Control modes Fig.
Page 15
7.7.3 Pump setting for underfloor heating systems 7.7.4 Pump setting for domestic hot-water systems Fig. 24 Selection of pump setting for system type Fig. 26 Selection of pump setting for system type Factory setting: AUTO Factory setting: AUTO ADAPT ADAPT Recommended and alternative pump settings according to fig.
7.8 Pump performance Relation between pump setting and pump performance Figure shows the relation between pump setting and pump performance by means of curves. See also section 11. Performance curves. Fig. 28 Pump setting in relation to pump performance Setting Pump curve Function The AUTO...
7.9 Bypass valve 8. Operating the product 8.1 Using automatic night setback BYPASS min. HA2 L AUTO Fig. 30 Automatic night setback activated Do not use automatic night setback when the pump is installed in the return pipe of the heating system. If you select speed I, II or III, automatic night setback is disabled.
For further information, see the ALPHA Reader documentation in 8.3.1 Activating manual summer mode Grundfos Product Center on www.grundfos.com. Activate the manual summer mode by pressing the automatic night setback button 3 to 10 seconds. See fig. 30. The green light 8.6 High-torque start...
9. Fault finding DANGER Electric shock Death or serious personal injury - Switch off the power supply before starting any work on the product. Make sure that the power supply cannot be accidentally switched on. CAUTION Pressurised system Minor or moderate personal injury - Before dismantling the pump, drain the system or close the isolating valves on either side of the pump.
10. Technical data and installation dimensions 10.1 Technical data Supply voltage 1 x 230 V ± 10 %, 50/60 Hz, PE Motor protection The pump requires no external motor protection. Enclosure class IPX4D Insulation class Relative humidity Maximum 95 % RH System pressure Maximum 1.0 MPa, 10 bar, 102 m head Liquid temperature...
10.3 Dimensions, ALPHAx 25-40 A, 25-60 A Dimensional sketches and table of dimensions. Fig. 34 ALPHAx 25-40 A, 25-60 A Dimensions Pump type ALPHAx 25-40 A 180 63.5 1 1/2 ALPHAx 25-60 A 180 63.5 1 1/2...
11. Performance curves 11.1 Guide to performance curves Each pump setting has its own performance curve. However, AUTO covers a performance range. ADAPT A power curve, P1, belongs to each performance curve. The power curve shows the pump power consumption in watt at a given performance curve.
12.3 ALPHA plugs 13.2 Application The new ALPHA SOLAR pump is designed to be integrated in all kinds of solar systems with either matched-flow or constant-flow rate. 13.3 Product description High-efficiency ECM pumps, such as ALPHA SOLAR, must not be speed-controlled by means of an external speed controller which varies or pulses the supply voltage.
The supply voltage is low. Make sure that there is sufficient voltage supply to the pump. <160 V Electrical error. Replace the pump and send the pump to the nearest Grundfos service centre. 230 V DANGER Electric shock Death or serious personal injury - Switch off the power supply before starting any work on the product.
When you use SIKON HE, you can replace the conventional transfer heat from the primary heat exchanger. 230-V UPS solar pumps by Grundfos ALPHA SOLAR pumps without having to change the controller to a high-efficiency pump Max.
Page 34
ALPHA SOLAR xx-75 130/180 >N3D@ >P@ Setting Max. head Curve 1 4.5 m Curve 2 5.5 m Curve 3 6.5 m Curve 4 7.5 m Setting Max. P 1 nom 4 >PñK@ Curve 1 19 W...
92 % recycling • 3 % incineration • 5 % depositing. Dispose of this product or parts of it in an environmentally sound way according to local regulations. For further information, see the end-of-life information at www.grundfos.com. Subject to alterations.