Trouble Shooting-Timer Controlled Water Softeners; Softener Fails To Regenerate; Softener Delivers Hard Water; Unit Uses To Much Salt - European Water Care EWC 10 Manual

Time clock or metered
Table of Contents

Advertisement

Note: Every single spare part no matter how small is available for this
water softener from EWC Ltd. Technical help is also available via the
telephone.
This means that this water softener, if looked after and
maintained properly, should give many years of reliable service.

Trouble Shooting-Timer Controlled Water Softeners

1/ Softener Fails to regenerate

2/ Softener delivers hard water

3/ Unit uses to much salt

4/ Loss of water pressure & Flow
5/ Loss of resin through drain line
Version 1. 1/12
a) Electrical Service Interrupted
b) Timer Defective
c) Timer regen pins not set correctly
a) Bypass valve open
b) No salt in brine tank
c) Injectors plugged
d) Insufficient water flowing
into brine tank
e) Internal valve leak
f) Salt bridged in brine tank
a) Improper salt setting
b) Softener regenerating too often
c) Excess water in brine tank
a) Inlet/outlet valves partially closed
b) Resin fouled with iron or organic
matter
a) Upper screen broken
15
Check Fuse
Replace Timer
Refer to commissioning instructions
Close bypass valve
Add salt to maintain level
above water level
Replace injectors screen
Check brine tank fill time- clean brine
line flow control
Replace seals / Spacers / Piston
Brine tank appears full of salt but is
not. Push a piece of wood into top
to collapse bridged salt
Check setting correct if required
Refer to commissioning instructions
Refer to problem 7
Check bypass valves & correct
Replace resin
Replace internal upper screen -

Hide quick links: