At the time of the burnout of the external sensor
Hot-air generator is stopped when the external sensor became the burnout of snapping of a wire etc. in the
case that the temp. of the place that parted is controlled by using the external sensor of the option.
●
Reverse connection by each sensor or detection of minus temp.
Hot-air generator is stopped at the time of the reverse connection of each temp. sensor (External sensor is
included) or perception of -15
Attention : Please block the source power supply (factory power supply) without fail when the
wiring is confirmed and readjusted at the time of abnormal.
"---" is flickered to HOT-AIR TEMP., "TC0" to
SETTING TEMP. (EXT. SENSOR lamp is being
lighted.)
《
《
゚
C. (Only inside temp. sensor is -10
"---" is flickered to HOT-AIR TEMP, display of each
sensor to SETTING TEMP
External sensor : Tc0
Overheat sensor
Inside temp. sensor
《
《
-14-
》
Main cause
・
Snapping of a wire of the external sensor
・
Snapping of a wire of the external sensor
compensating wire
・
Miss of the inlet sensor wiring terminal
》
Return method
Please disarm by pushing STOP switch after the
confirmation of the external sensor.
゚
C.)
: TcM
: Tcb
》
Main cause
・
Reverse connection of the external sensor
・
Reverse connection by the wiring readjustment of
each sensor
・
Atmosphere temp. or suction temp. of minus
》
Return method
Please disarm by pushing STOP switch after the
confirmation of the external sensor or the
improvement of the minus condition. Please
order the repair about except for reverse
connection of the external sensor.
Outlet sensor
: TcA
Inlet sensor
: Tcc