Type 2 bit priority
Fig. 185:
Parameter window: "Group member, Data type 2 bit priority"
Object value
Options:
Free/
Forced ON/
Forced OFF
This parameter is used to select which object value is sent. The priority
control function is explained in the following table:
Bit 1
Bit 0
Access
Description
0
0
Free
The priority object has enabled e.g. the switch actuator.
The output switches depending on the value of the switch object.
0
1
Free
1
0
OFF
The priority object has switched e.g. the switch actuator OFF with
priority control. The switch object has no function.
1
1
ON
The priority object has switched e.g. the switch actuator ON with
priority control. The switch object has no function.
Table 12:

Priority object

Note:
4 different values can be sent with the telegram. So-called
priority objects can thus be addressed in the EIB devices. If a
channel e.g. in a switch actuator should switch on or off, the
value 1 or 0 is sent to the assigned switch object. If a priority
object is also assigned to this channel, the value that was sent
to the priority object defines the behaviour of the channel.