Canovate Can BREEZE Series Operating And Maintenance Instructions Manual

Canovate Can BREEZE Series Operating And Maintenance Instructions Manual

Cooling unit

Advertisement

Quick Links

IT's
far and away
the
BEST
Can BREEZE
Operating and Maintenance of
Cooling Unit Instructions
8-14 kW

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Can BREEZE Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Canovate Can BREEZE Series

  • Page 1 IT’s far and away BEST Can BREEZE Operating and Maintenance of Cooling Unit Instructions 8-14 kW...
  • Page 2 (including but not limited to software, audio, video, text, and photographs) rests with Canovate or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.
  • Page 3: Table Of Contents

    Contents Canovate Legal Disclaimer 10.1 TAKE OUT THE FILTER Contents 10.2 CLEAN THE FILTER General Information 10.3 RESET OF FILTER INDICATION Save these instructions OUTDOOR UNIT Intended users 11.1 Important Notice Legal information concerning the TRANSPORTATION AND HANDLING operating instructions...
  • Page 4: General Information

    Legal information concerning the operating instructions We reserve the right to make changes in content. Canovate is not responsible for mistakes in this documentation. Liability for indirect damages which occur through the delivery or use of this documentation is excluded to the extent allowable by law.
  • Page 5: Proper Use

    - Improper rectifi cation of malfunctions. - Use of replacement parts which are not authorised by Canovate Safety Instructions The Front Coolers produced by Canovate are developed and produced with due regard to all safety precautions. Nevertheless, the unit still causes a number of unavoidable dangers and risks.
  • Page 6: Important Safety Instructions

    It is vital that the manufacturers’ consent is obtained before adding anti-freeze! Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 7: Service And Technical Staff

    Equipment (RoHS) of 13 February, 2014. Note: Corresponding information concerning the RoHS directive is provided by our fi rm on the Internet at www.canovate.com www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 8: Transport And Handling

    • If using a forklift or pallet jack, ensure that the fork tine length is suitable to safely move the packaged module. • Canovate recommends keeping the module in the protective packaging until it has been moved to the installation site.
  • Page 9: Unpacking

    Damage should be immediately reported to the carrier and a damage claim fi led with a copy sent to Canovate or to your sales representative. If you later fi nd any concealed damage, report it to both the shipping company and your local Canovate representative.
  • Page 10 Remove the Stabilizers at the corners Remove the bag when ready to install the Front Cooler. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 11: Components

    11 Adjustable Feet Components of Fan Unit 1 Fan Motor 2 Fan 3 Fan Case 4 Electrical Control Box 5 Rail of Fan www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 12: Units Installation

    fi re or failure, etc., may occur. UNIT INSTALLATION 7.1.1 F A C T O R Y - S U P P L I E D ACCESSORIES Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 13: Initial Check

    The insulation for the drain pipe must be selected to insure vapor sealing and prevent condensation forming. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 14: Drain Pipe Connection

    4. Insulate the drain hose around the wire clamp to prevent any condensation as shown. Wire Clamp A Drain Hose Wire Clamp b Drain Boss Insulation Drain Pipe Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 15 4. Wrap the insulation material around the connecting part perfectly. 5. Fasten the drain pipe to the connecting part using the factory-supplied clamp. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 16: Electrical Wiring

    Single phase connection Remote Control (PC-ART) Transmission Wires Power supply wires (Single phase) Earth Screw Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 17: Settings Of Dip Switches

    1 2 3 4 1 2 3 4 Setting Position 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 18 No setting is required. This switch is utilized for setting the model code which corresponds to the indoor unit type. Indoor Unit Model DSW4 Setting 1 2 3 4 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 19: Maintenance

    1. Side the knobs. Knob 2. Open the air inlet grille. 3. Take out the air fi lter from the air inlet grille. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 20: Clean The Filter

    After cleaning the air fi lter, press the “RESET” button. The FILTER indication will disappear and the next fi lter cleaning time is set. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 21: Outdoor Unit

    • No part of this manual may be reproduced without written permission. • If you have any questions, contact your service contractor of Canovate. • This manual gives a common description and information for this air conditioner which you operate as well as for other models.
  • Page 22 The high pressure switch is indicated on the electrical wiring diagram in the outdoor unit as PSH connected to printed circuit board (PCB1) in the outdoor unit Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 23: Transportation And Handling

    Turn OFF the main switch when the system is to be stopped for a long period of time: If the main switch www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 24: Automatic Controls

    At this time the lover is fi xed horizontally. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 25: Basic Troubleshooting

    -- Check if the temperature condition is not within the operating range. Abnormal swing louver’s position Check if the four louver’s position at the air outlet are in same www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 26 Except for a long period of shutdown, keep the main switch ON, since the oil heater is energised when the compressor is stopped. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 27: Name Of Parts Outdoor Unit

    Check Joint Electrical box High pressure switch for protection Pressure switch for control Silencer Crankcase heater Vibration absorbing rubber (3pcs.) Air outlet Air inlet www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 28 Stop valve for liquid line Silencer R410A 4.15 MPa Connection by Connection by Leakage test Gas refrigerant or cooling for heating welding pressure Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 29: Unit Installation

    Install the unit in a restricted area not accessible by the general public Aluminium fi ns have very sharp edges. Pay attention to the fi ns to avoid injury www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 30: Installation Space

    200 or more of the back space is acceptable when the right and Allow 100 mm of space between units. Leave open both right and left sides. left sides are open. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 31 The length A is as shown in the following table: When L Close the base not to allow the outlet air bypassed. 0 < L 600 or greater 1400 or greater www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 32: Installation Place Provision

    When installing the outdoor unit on a fi eld supplied frame, use metal plates to adjust the frame width for stable installation as shown in below fi gure. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 33 Outdoor unit is stable Frame 100mm or more Metal plate Recommended Metal Plate Size (Field-Supplied) Material: Hot-Rolled Mild Steel Plate (SPHC) Plate Thickness: 4.5 T www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 34: Refrigerant Piping

    N O T E A system with no moisture or oil contamination will give maximum performance and lifecycle compared Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 35: Suspension Of Refrigerant

    Do not fi x the refrigerant piping directly with the metal fi ttings (The refrigerant piping may expand and contract). Some examples for suspension method are shown below. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 36: Piping Connection For

    fi gure. • Slowly press down the cover. NOTE Hold the cover with a hand to remove screws as the cover may fall down. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 37 Remove the rear pipe cover under the rear cover and remove part following the slit. Mount the piping cover in order to avoid water www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 38 Operation of stop valve should be performed according to the fi gure below. Close before shipment Outdoor unit stop valve Spindle Type 8-14 kW Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 39 C A U T I O N At the test run, fully open the spindle and ball stop valve. If not fully opened, the devices will be damaged. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 40 & Nitrogen blow face by the low pressure Manifold during brazing) gauge Vacuum cylinder Example of Evacuation and Refrigerant Charge. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 41: Refrigerant Charge

    1 Determine an additional refrigerant quantity according to the following procedure, and charge it into the system. 2 Record the additional refrigerant quantity to facilitate service activities thereafter. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 42: Electrical Wiring Connection For Outdoor Units

    O.U. to I.U. or I.U. toI.U. 1 to1, 2 to 2 Remote Control DC inverter I.U. to I.U. A to A, B to B Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 43: Setting Of Dip Switches For Outdoor Unit

    Quantity and Position of DIP Switches. The location is as follows: DSW1: For Test Run Factory setting DSW2: Optional Function Setting Factory setting Optional function setting Optional function setting www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 44 For IVX series For simultaneous operation DSW4 Factory setting (Setting for the ten digit). DSW6: Not available for ES series Factory setting RSW1 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 45: System Installation Dip Switch Setting

    It is required to set dip switches of every indoor unit and outdoor unit and match of the transmission circuit impedance. • Dip Switch Setting Example: www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 46 Indoor Unit Address the setting of other indoor units in the same refrigerant cycle. (If not set, RSW1 the automatic address function is performed). Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 47: Test Running

    Check whether or not the electrical wiring of the indoor units and the outdoor units are connected as shown in the chapter Electrical Wiring. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 48 In the case of anual cooling optional function, cut JP1 out and set the DSW6-1 to OFF. (Individual control is not available when anual cooling is selected). Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 49: Test Run Procedure By Remote

    TEST RUN operation time can be modifyed / increased depressing the time switch in the Remote Control. Go to www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 50: Test Run From Outdoor Unit

    ON and the outdoor unit is operated. • Turn all DIP switches of DSW1 OFF when the test run opera- tion is completed. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 51 3.3 MPa (33kgf/ Manual Defrost Operation Finishes G) or Thermo-OFF. Defrost operation is automatically ended and the heating operation is started. www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 52: Specifi Cations

    Cooling: Internal ambient 27°C (19°C WB) - Ambient 35°C; Refrigerant piping length 7.5m, level difference 0m. Sound pressure level measured at 1.5 meters below the unit (measured in anechoic room) Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com...
  • Page 53: Troubleshooting

    Others COOL MED COOL MED ond alter- ADDS. RN ADDS. RN 2, 3 and 4 indoor units nately system ALARM ALARM www.canovate.com info@canovate.com P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 54 Incorrect address No. Setting or refrigerant Over 64 indoor units setting by No. or indoor unit address. setting cycle Compressor Compressor protection alarm Failure of compressor. Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW www.canovate.com info@canovate.com P. +90 216 484 2222...
  • Page 55 P. +90 216 484 2222 Can BREEZE Operating and Maintenance Cooling Unit Instructions 8-14 kW...
  • Page 56 :www.canovate.com © Copyright 2016 Canovate Group, The information contained herein is subject to change without notice. The only warranties for Canovate products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty.