Grounding The System; Grounding With A Grounding Device - Siemens Sinamics SM150 6SL3845-2NN41-8AD0 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

9.2

Grounding the system

Electric shock even after shutdown
High voltages can still be present even after shutdown. Touching the device can result in death
or serious injury.
● Only work on the power unit if it has been sufficiently grounded. Before touching the device,
● Always observe the five safety rules (Page 15) when carrying out any work on the device.
9.2.1

Grounding with a grounding device

Use a three-pole grounding harness for fixed ball points to ground the system. When ordering
a grounding harness, contact Service & Support.
Use a sufficient number of grounding harnesses corresponding to the configuration. A
grounding harness is required for each three-phase system.
Attaching the grounding spider
Secure the terminals of the grounding spider, first on the lower ball button
upper ball buttons
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE
WARNING
carefully ensure that the power unit is in a no-voltage condition:
.
Ball head in the cabinet
Ball buttons in the motor cabinet
Maintenance
9.2 Grounding the system
, and then on the
135

Advertisement

Table of Contents
loading

Table of Contents