Siemens SIMATIC S7-1500 Function Manual page 48

Isochronous mode
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Signal sequence in the OIP model
The following figure shows the signal sequence in the OIP model from the acquisition of
process values and the processing in the CPU to the output of the process values: The
application cycle is twice as long as data cycle T_DC in this example.
Execution of isochronous mode interrupt OB
"SYNC_PI" instruction
"SYNC_PO" instruction
Isochronous read-in of process values on I/O module at time T
Isochronous output of process values on I/O module at time T
Figure 6-2
Signal sequence in the OIP model
At time T
over 2 application cycles in the OIP model. The output data is always available on the I/O in
the following application cycle at time T_DC + T
With the IPO model, there is a constant execution time from the "input terminal" to the
"output terminal" of T
T
+ 2 x application cycle + T_DC + T
I
Isochronous mode
Function Manual, 10/2018, A5E43884988-AA
the process values are read in isochronously on the I/O. The data is processed
I
+ application cycle + T_DC + T
I
6.2 Program execution according to the OIP model
I
O
.
O
.
O
can be ensured as the process reaction time.
O
Programming isochronous mode
47