8.3.2
Programmable Features
• Always return the door to the fully closed position before performing any program settings.
Maximum Run Timer
Maximum run timer is set to 90 seconds by default. When programmed, this feature calculates the total time required
for the door to travel from the fully closed to the fully opened position and adds 5 seconds to this time. Therefore, if
the door is obstructed while travelling up or down, this feature will stop the operator after the maximum run timer time
has elapsed.
Run Timer Programming
1. Verify if the close limit switch is activated and
if the close LED is ON.
2. Set select switch on D = Run Tm.
3. Press the "Open" button and let the door
reach the fully opened position.
Result: 10 sec is added to the total travel
time.
4. Set select switch on run mode
(0, 1, 2, 3, 4 or 5).
Timer to Close (TTC)
Timer to Close (T = 4 or TS = 5 Mode), will close the door from the fully opened and mid-stop positions after a
factory preset time (5 sec.). Timer to Close can be programmed in increments of 1 sec. or 15 sec.
TTC Programming
1. Verify if the close limit switch is activated
and if the close LED is ON.
2. Set select switch on B = Tm Cls.
3. Press the "Stop" button to return the time to
0 sec. or to reprogram.
4. Press the "Open" button to add 15 sec.
increments, or press the "Close" button to
add 1 sec. increments. Max. 4 min.
5. Set select switch on T = 4 or TS = 5.
Refer to Run Mode Settings section, p. 24
for mode descriptions.
Timer to Close User Suspension Feature
This feature allows the Timer to Close to be enabled/disabled from the floor by using a wall push-button control
station. This feature allows the user to keep the door opened for ONE CYCLE only.
TTC Deactivation
While the door is in the closed position, press the push-
button control station's "Stop" button 3 times and then
the "Close" button 3 times consecutively. This will
deactivate the TTC (TTC is suspended).
For technical support, please call 1-800-361-2260 or visit
25
NOTICE
Select Switch
1. Verify if the close limit switch is activated
and if the close LED is ON.
2. Set select switch on D = Run Tm.
3. Press the "Stop" button.
Result: The max. run timer is set to the
default value of 90 sec.
4. Set select switch on run mode
(0, 1, 2, 3, 4 or 5).
Select Switch
1. If the TTC is not required, set select switch
on run mode (0, 1, 2, or 3).
The TTC is re-activated (TTC returns to normal
function) once the door is fully closed.
www.manaras.com
Set Run Timer to Default
TTC Deactivation
TTC Activation