Sw Mode & Address Setting; Sw Mode Setting - Panasonic 1735 Technical Description

Alert annunciation units
Hide thumbs Also See for 1735:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
6
6.1
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
SW mode & Address setting
Alert Annunciation Unit 1735 can run in SW mode 1735 - 1587 only.
It shall also have a unique address on the RS485 line connected to the
1587 board in the EBL512 c.i.e. See EBL512 Planning Instructions.
Alert Annunciation Unit 1736 can run in SW mode 1736 - 1587 only.
It shall also have a unique address on the RS485 line connected to the
1587 board in the EBL512 c.i.e. See EBL512 Planning Instructions.
The SW mode 1736 – 1587 shall be used in system EBL128 and an
optional RS485 transceiver component 4552 is required on the main
board in the EBL128 c.i.e. It shall also have a unique address on the
RS485 line connected to the main board connector "J1". See EBL128
Planning Instructions.
The SW mode 1736 – 1587 shall be used in system EBL512 G3. It
shall also have a unique address on the RS485 line connected to the
main board connector "J4". See EBL512 G3 Planning Instructions.

SW mode setting

A brand new AA unit has no SW mode. It is factory set to "Not
selected" (and is hereby not addressable). When it is powered it will
automatically be ready for the "SW mode setting".
As an alternative, an AA unit in operation
mode setting" via the jumper "J4" in the unit. See the following
chapter.
When the AA unit is ready for the "SW mode setting" this is indicated
by the LED "L2" (Alarms queued). The back-light is turned on and
the following information is shown in the display:
MODE SETTING!
Type: xxxxxxxxxxxx
XXXXXXXXXXXX
can be changed to one of the following:
- 1735 – 1587 (1735 only)
- 1736 - 1587 (1736 only)
- 1826 – 1587 2
nd
Cab
- 1826 – 1582 2
nd
Cab
- 1826/28 - 1587
- 1826/28 - 1582
- 1728 - 1587
- 1728 - 1582
- Not selected
Scroll to the wanted SW mode with the push button "P1" (black).
Store the selected SW mode with the push button "P2" (yellow) and
15
Or when a unit, not in operation but with the mode and address set before,
is powered.