Emerson Copeland EazyCool OMQ-56-Nxx-TWD Series Application Manuallines page 20

Outdoor condensing units for refrigeration networks
Table of Contents

Advertisement

Use a double-tipped torch
End of tube
During brazing
protect housing
with a damp cloth
Brazing of the tubes:
For brazing of the tubes see illustration below and the following procedures:
Fit the copper tube into the compressor tube.
1.
2.
3.
4.
NOTE: The time spent heating area 3 should be minimal. As with any brazed joint,
overheating may be detrimental to the final result.
To disconnect:
Heat joint areas 2 and 3 slowly and uniformly until solder softens and tube can be pulled
out of the fitting.
To reconnect:
See the procedure above.
C6.1.4/0305/E
Condensing Unit For Refrigeration Networks
Sectional view
During brazing pull
back line insulation.
Heat area 1. As the tube approaches brazing temperature:
Heat area 2 until braze temperature is attained. It is necessary
to heat the tube evenly. Move the torch up and down and
rotating around the tube.
Add braze material to the joint while moving the torch around
the joint to flow braze material around the circumference.
Then heat area 3. This will draw the brazing material down into
the joint.
19
Part no: 3136433