8-3. INDOOR – OUTDOOR CONNECTING CABLE
Outdoor power supply
Indoor unit-Outdoor unit
Note: The maximum cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Note: The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
8-4. M-NET WIRING METHOD
Points to notice:
2
Centralized
controller
OCH567
Max. 164 ft [50 m]
Max. 147 ft [45 m]
3 o AWG13 (polar)
3 o AWG15 (polar)
Refrigerant
address 00
M-NET
address 01
Power
supply unit
A-control
remote
controller
O
Bad example (Multi spot earthing of shield wire)
Centralized
controller
supply unit
M-NET transmission wire
Good example 1 (Single spot earthing of shield wire)
Centralized
supply unit
controller
M-NET transmission wire
Good example 2 (Single spot earthing of shield wire)
Centralized
supply unit
controller
M-NET transmission wire
Wire No. o Size
Max. 262 ft [80 m]
3 o AWG13 (polar) and S3 separated
Wire No. o Size
Max. 393 ft [120 m]
2 o Min. AWG22
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
Power
M-NET type
M-NET type
outdoor unit
outdoor unit
Power
M-NET type
M-NET type
outdoor unit
outdoor unit
Power
M-NET type
M-NET type
outdoor unit
outdoor unit
Refrigerant
address 00
M-NET
address 03
A-control
remote
controller
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
-