Disposal - Grundfos SI 001 PSU Installation And Operating Instructions Manual

Sensor interface
Table of Contents

Advertisement

5. Technical data
Supply voltage
Supply voltage
Frequency
Power consumption
Cable size
Transmitter cable
Recommended cable type
Controller
Controller connection
Recommended cable type
Supply cable
Conductor size
Diameter
AWG
[mm]
17
1.15
18
1.02
19
0.91
20
0.81
21
0.72
22
0.64
23
0.57
Other data
Enclosure class
Cable entry
Ambient temperature
During operation
During storage
During transportation
During operation, the interface must
Caution
not be exposed to direct sunlight.

6. Disposal

This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.
115-400 VAC ±10 %
50-60 Hz
Maximum 7 W
2
IEC: 0.75 - 4 mm
UL: 19-12 AWG
Screened
Cross-section: 0.25 - 1 mm
AWG: 24-18
Maximum cable length: 30 m/100 ft
2-wire, 4-20 mA
Screened, twisted-pair
Cross-section: 0.25 - 1 mm
AWG: 23-18
Cross-sectional
Resistance load 500 Ω
2
area [mm
]
1.04
0.82
0.65
0.52
0.41
0.33
0.26
IP54
6 x M16 Ø4 - Ø10
–20 °C to +50 °C (–4 °F to +122 °F)
–20 °C to +70 °C (–4 °F to +158 °F)
–20 °C to +70 °C (–4 °F to +158 °F)
2
2
Maximum cable length [m]
Resistance load 250 Ω
4834
3040
1912
1202
756
476
299
10877
6840
4302
2706
1702
1070
673
Subject to alterations.
7

Advertisement

Table of Contents
loading