Installation Kit; Installation; Wall Mounting; Mounting In Control Cabinet - Grundfos SI 001 PSU Installation And Operating Instructions Manual

Sensor interface
Table of Contents

Advertisement

3. Installation kit

The SI package contains these parts:
interface with six screwed cable entries with
blanking plugs
DIN rail clip with screws
installation and operating instructions
Quick Guide.

4. Installation

The interface unit can be mounted on a wall or on a
DIN rail in a control cabinet.

4.1 Wall mounting

Mount the interface on the wall. See fig. 2 and the
drilling template in the Quick Guide to the interface.
91 mm
Fig. 2
Wall mounting of the interface

4.2 Mounting in control cabinet

When the interface is mounted in a control cabinet
containing a frequency converter, it is especially
important to ensure an EMC-correct installation of
both the interface and frequency converter.
The following rules must therefore be observed:
All cable screens must be connected to earth. If it
is not possible to use cable clamps, the stripped
part of the cable screen must be as short as
possible to reduce the impedance at high
frequencies.
All units in the control cabinet must be connected
to earth.
Mounting on DIN rail
The interface is prepared for mounting on a 35 mm
DIN rail (EN 50022).
1. Fix the DIN rail clip supplied on the interface.
See the instructions on the interface.
2. Fit the interface by hooking the top on the DIN rail
and clicking the bottom onto the rail. See fig. 3.
Fig. 3
Dismounting from DIN rail
Remove the interface by pulling it downwards and
free of the DIN rail.

4.3 Electrical connection

The electrical connection should be carried out by an
authorised electrician in accordance with local
regulations.
Ø 4.5 mm
Caution
Note
Sensor interface on DIN rail
Warning
Before beginning the electrical
connection, make sure that the
electricity supply has been switched off
and that it cannot be accidentally
switched on.
Supply voltage to the interface:
115-400 VAC 50-60 Hz, ±10 %.
If the supply cable to the interface has
no earth conductor, a separate earth
connection must be connected to the
internal earth terminal.
See fig. 4, pos. 4.
5