M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

MOUNTING POSITION

The actuator may only be mounted beside or above the
valve. Adjust the valve in the correct position before
mounting the actuator.
Fig. 1. Mounting positions
MOUNTING
Before the actuator is fixed to the valve, the adjustment cap
must be removed (Fig. 2). Make sure that the actuator is in
the open position (factory-supplied position) before fixing the
actuator to the valve body.
Fig. 2. Remove protection cap
The actuator must be mounted by hand. Do not use tools or
additional force insofar as this may damage the actuator and
valve.
Fig. 3. Mounting the actuator

SWITCH SELECTION

The built-in selector switches must be set according to the
valve type (2-way or 3-way), valve size, and the controller
output signal (0...10 V or 2...10 V), see Fig. 4.
Y=+10V=
closes
A
B
factory
setting
opens
Y=+10V=
A
B
opens
Y=+10V=
A
AB
B
Fig. 4. Selecting valve type and output signal

ELECTRIC WIRING

The electrical installation must comply with Fig. 5.
INPUT SIGNAL OVERRIDE
To override the controller output signal, the input signal must
be connected to COM (0 %) or 24 V (100 %) using an
external switch (see Fig. 5).
Fig. 5. Connection of input switch
3
100%...0%
Y = 0...+10V
0%...100%
0...10V
factory
2...10V
setting
Y = 2...+10V
EN0B-0097GE51 R1004