Rockwell Automation Allen-Bradley PowerFlex 70 Quick Start Manual
Rockwell Automation Allen-Bradley PowerFlex 70 Quick Start Manual

Rockwell Automation Allen-Bradley PowerFlex 70 Quick Start Manual

Connect drives over a devicenet network
Hide thumbs Also See for Allen-Bradley PowerFlex 70:

Advertisement

Quick Links

Quick Start
Logix5000 Control Systems: Connect PowerFlex 70 Drives
over a DeviceNet Network
Catalog Numbers Logix5000 Controllers, PowerFlex 70 Drives

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Questions and answers

Summary of Contents for Rockwell Automation Allen-Bradley PowerFlex 70

  • Page 1 Quick Start Logix5000 Control Systems: Connect PowerFlex 70 Drives over a DeviceNet Network Catalog Numbers Logix5000 Controllers, PowerFlex 70 Drives...
  • Page 2 IMPORTANT Identifies information that is critical for successful application and understanding of the product. Allen-Bradley, CompactLogix, ControlLogix, Integrated Architecture, KwikLink, Logix5000, PowerFlex, Rockwell Software, Rockwell Automation, RSLogix, RSNetWorx, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
  • Page 3: Table Of Contents

    ..............51 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 4 Table of Contents Notes: Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 5: Before Using This Publication

    CompactLogix 5370 L3 control system and it is powered. For more information on how to complete these tasks with specific Logix5000 controllers, see  the Integrated Architecture : Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 6 This task does not include installation of remote hardware components, for example, PowerFlex 70 drives, used over the network included in your application. Prepare the computer Installing required software, for example RSLogix 5000 software, on your complete Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 7 IMPORTANT: For more information on how to create an RSLogix 5000 project that can be associated with your DeviceNet configuration file, see Associate the DeviceNet Configuration File with an RSLogix 5000 Project. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 8: Other Logix5000 Control System Quick Starts

    What You Need - This section lists the tools that are required to complete the tasks in the • current chapter. This includes, but is not limited to, hardware and software. • Follow These Steps - This section illustrates the steps in the current chapter. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 9: Where To Start

    4. Create RSNetWorx for DeviceNet and RSLogix 5000 Software Projects Logix5000 Controller Prepare the PowerFlex 70 Drive Hardware page 13 Create DeviceNet Network Software Files page 21 Use a PowerFlex 70 Drive in an RSLogix 5000 Project page 41 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 10: How Hardware Is Connected

    CompactLogix 5370 L3 control system. CompactLogix 5370 control systems require RSLogix 5000 software, version 20.00.00 or later. If you connect a PowerFlex 70 drive over a DeviceNet network in a Logix5000 control system that uses a different controller, the minimum software version may differ. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 11: Parts List

    Provides details about adding and configuring modules, establishing communication, and writing ladder logic. Programming Manual, publication 1756-PM001 ® Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell Automation industrial system. publication 1770-4.1 Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.
  • Page 12 Preface Notes: Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 13: Before You Begin

    DeviceNet network are powered. Prepare the computer • Configure the network • Create an RSLogix 5000 project - The example RSLogix 5000 project used in this quick • start uses a CompactLogix 5370 L3 controller. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 14: What You Need

    18 Connect the Drive Wire Power to to the DeviceNet the Drive Network Motor page 15 page 19 AC L1 AC L2 AC L3 Set the Node Address and Communication page 17 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 15: Mount The Drive

    1. Loosen the screw and remove the cover. 2. Verify that a jumper is installed between I/O terminals 7 and 8. 3. If there is no jumper between I/O terminals 7 and 8, install one before proceeding. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 16 AC L1 AC L2 AC L3 Motor Chassis ground AC L1 AC L2 AC L3 For complete information on wiring a PowerFlex 70 drive, see the PowerFlex 70 AC Drives User Manual, publication 20A-UM001. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 17: Set The Node Address And Communication Rate

    This quick start uses a node Tens Digit Ones Digit address 1. 2. Use a small screwdriver in the same manner to set the DeviceNet 500K adapter’s communication rate. 250K 125K AUTO This quick start uses 125 Kbps. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 18: Connect The Devicenet Adapter To The Drive

    DPI connector on the adapter. Internal Interface Cable 2. Fold the cable behind the adapter without creasing it and mount the Adapter adapter on the drive by using four captive screws. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 19: Connect The Drive To The Devicenet Network

    P1F5-R5 KwikLink right-angle micro male to micro female connector cable. 3. Route the connector cable through the hole in the bottom of the drive and connect it to the DeviceNet connector on the adapter. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 20 Chapter 1 Prepare the PowerFlex 70 Drive Hardware 4. Place the cover on the drive and tighten the screw. 5. Connect the drive to the DeviceNet network. 6. Apply power to the drive. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 21: Before You Begin

    Before you begin, you must complete these tasks: These tasks described in Before Using This Publication on page • Prepare the Logix5000 control system hardware – Prepare the computer – Configure the network – Create an RSLogix 5000 project – Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 22: What You Need

    Configuration File with an RSLogix 5000 Project page 23 page 29 Set the 1769-SDN Scanner Module’s Node Address Create a page 26 DeviceNet Scanlist page 35 Create a DeviceNet Configuration File page 29 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 23: Register An Eds File - Optional

    If you do not need to register an EDS file in RSNetWorx for DeviceNet software, skip to Set the 1769-SDN Scanner Module’s Node Address on page 1. Access the Rockwell Automation website that provides access to EDS files at: http:// www.rockwellautomation.com/resources/eds/.
  • Page 24 Create DeviceNet Network Software Files 6. When the EDS dialog box appears, click Next. 7. Verify that Register an EDS file(s). is checked and click Next. 8. Browse to the EDS file and click Next. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 25 10. Select the graph image for the device you want to register and click Next. 11. Select the device you want to register and click Next. 12. Click Finish when the registration is successful. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 26: Set The 1769-Sdn Scanner Module's Node Address

    For example purposes, the scanner module’s node number is 3 before it is changed. 1. Verify the controller’s mode switch is in the PROG position. PROG 2. Start RSNetWorx for DeviceNet software. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 27 EtherNet/IP network or USB connection. This example uses an EtherNet/IP network connection. 5. Under the AB_ETHIP-1 driver, expand the path to the 1769-SDN scanner module as shown in the example graphic. 6. Click OK. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 28 8. Enter a node address of 1 for the 1769-SDN scanner module and click Apply. The Address is applied and is confirmed in the Messages box. 9. Record the node address. 10. Click Close. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 29: Create A Devicenet Configuration File

    Create a DeviceNet Configuration File 1. From the File menu, choose New. 2. Click Who Active to go online. 3. Expand the networks to the appropriate DeviceNet network. In this example, the network is Port 2, DeviceNet. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 30 1. Once the software browses the DeviceNet network to recognize the two nodes installed while completing the tasks described in this quick start, you can click Cancel and the browse function ends. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 31 All configuration is cleared from the scanner module, and the software is synchronized with the module. IMPORTANT If you receive a fault message on your PowerFlex 70 drive, press on the keypad to clear the fault. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 32 11. Enter the slot number of the 1769-SDN scanner module. 12. Click OK. 13. Save the file and record the file name and path. This quick start uses the example file name DeviceNet.dnt. 14. Close RSNetWorx for DeviceNet software. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 33: Rslogix 5000 Project

    I/O configuration. This example uses a 1769-SDN scanner module in a CompactLogix 5370 L3 controller project. 4. Configure the scanner module’s parameters on the General and Connection tabs as desired. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 34 Open. 6. Click OK. 7. Save the RSLogix 5000 project and download it to your Logix5000 controller. This example uses the name PFlex70_Drive_on_DeviceNet_quick_start.acd 8. Go offline but leave the RSLogix 5000 project open. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 35: Create A Devicenet Scanlist

    The RSNetWorx for DeviceNet launches and opens the DeviceNet configuration file associated with your RSLogix 5000 project. 5. From the Network menu, choose Online. 6. If prompted to upload or download device information, click OK. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 36 7. Right-click the PowerFlex 70 drive and choose Download to Device. 8. When prompted to continue configuration download, click Yes. The configuration downloads to the PowerFlex 70 drive. 9. Right-click the PowerFlex 70 drive and choose Properties. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 37 In real-world applications, the drive is always connected to, and controls, a motor. In that case, you must change additional parameters, for example, parameters 41…45. 13. Click OK. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 38 Yes. 15. Right-click the 1769-SDN scanner module and choose Properties. 16. Click the Scanlist tab on the 1769-SDN Scanner Module dialog box. 17. When prompted to upload or download the configuration, click Upload. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 39 19. Click the right arrow to move the PowerFlex 70 drive to the Scanlist. 20. Click OK. 21. When prompted to download changes, click Yes. 22. Click OK. 23. Save the file and close RSNetWorx for DeviceNet software. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 40 Chapter 2 Create DeviceNet Network Software Files Notes: Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 41 Create a DeviceNet Configuration File on page If you use a different Logix5000 controller and DeviceNet scanner module, you can complete the tasks in this chapter but must account for any software differences. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 42: Before You Begin

    – These tasks described in Chapter Create DeviceNet Network Software Files on page • Set the 1769-SDN Scanner Module’s Node Address – Create a DeviceNet Configuration File – Create a DeviceNet Scanlist – Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 43: What You Need

    DeviceNet Tag Generator tool in RSLogix 5000 software • RSLogix 5000 software • Follow These Steps Create DeviceNet Tags page 44 Download the Project page 44 Test the PowerFlex 70 Drive Tags page 48 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 44: Create Devicenet Tags

    1. Launch the DeviceNet Tag Generator tool. 2. Select your RSLogix 5000 project and click Select Scanner. 3. Select the 1769-SDN scanner module that scans the network where the device is located and click Select RSNetWorx Project. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 45 Use a PowerFlex 70 Drive in an RSLogix 5000 Project Chapter 3 4. Select the main DeviceNet configuration file and click Select Scanner Node. 5. Select the node of the DeviceNet scanner module and click Generate Tags. 6. Click Generate Tags. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 46 When tag generation is complete, the text log appears. 8. Close the DeviceNet Tag Generator. The DeviceNet Tag Generator created new programs and tags that were added to the controller organizer in your RSLogix 5000 project. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 47: Download The Project

    4. On the Download dialog box, click Download. The project downloads to the controller. If you receive a fault IMPORTANT message on your PowerFlex 70 drive, press on the keypad to clear the fault. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 48: Test The Powerflex 70 Drive Tags

    3. Change the O.CommandRegister.Run tag to 1. The 1769-SDN scanner module transitions to Run mode. 4. If you receive a fault message on your PowerFlex 70 drive, press on the keypad to clear the fault. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 49 POL_O.Start tag to 1. The display on the drive registers the speed increase in Hertz until the value entered at the reference tag is reached. 7. Change the O.Start tag back to 0. Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 50 9. Change the Stop tag back to 0. 10. Select Go Offline. By starting and stopping the drive, you verified the following: The controller is correctly communicating with the drive. • The drive can receive simple commands. • Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 51 11 1485P-P1E4-R5 KwikLink sealed micro connector 11 1769-SDN scanner module 26 node address 1799-DNC5MMS 5-pin linear to micro male adapter 11 set on 1769-SDN scanner module 26 set on 20-COMM-D DeviceNet adapter 17 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 52 10 prerequisite tasks 6 use tags 48 RSNetWorx for DeviceNet software 7 configuration file 29 configure scanlist 35 register an EDS file 23 requirements 10 set node address on 1769-SDN scanner module 26 Rockwell Automation Publication IASIMP-QS030A-EN-P - July 2012...
  • Page 54 Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640...

This manual is also suitable for:

Allen-bradley logix5000

Table of Contents