Led Codes; Troubleshooting - Delta AlertMaxx DMS-270 Installation & Operating Instructions Manual

Pump station high level alarm for ground water and foul water
Table of Contents

Advertisement

AlertMaxx

13.0 LED codes

Beep
1/sec
1/min
1/min

14.0 Troubleshooting

The unit does not turn on
The LEDs flash in the following order, red, blue,
green
The red LED is on continuously and the blue LED
flashes every second
The alarm does not activate when the float switch
is lifted
The alarm does not activate when pressing the
'TEST' button.
Alarm continuously active
14
Red LED
Blue LED
3/sec
3/sec
1/5sec
1/sec
On
1/sec
All flash in sequence
1/sec
Various
Fault
Green LED
1/sec
None
High water level
High water level but has been reset
2/sec
High water level has occurred
1/sec
No mains power
1/sec
Pump station service required
Float or cabling error
Low/flat battery
Battery too flat to start up
Various
Internal errors
Battery is flat - charge the battery by connecting
mains supply to alarm unit
Still doesn't turn on after 3 mins - alarm unit is
faulty
Low battery - charge the battery by connecting
mains supply to alarm unit
Float switch cable is faulty - check float switch
connections and cable for damage
Float switch is broken - replace float switch
Float cable is broken - replace float switch
Faulty unit
Pendant float has been incorrectly wired - check
the blue and black cables are connected correctly
For technical support, please call 01279 757400
Fault
Cause