4.2. Setting the Desired Temperature in the Cooling Mode

In the cooling mode (i.e. when you select the Reg. P, Reg. T*, or Reg.Tx function), this
menu allows you to set the value of the output or evaporation temperature in the range of
−10.0ºC to +55.0ºC. The factory preset temperature is +10°C. In the slave mode, the target
value is not being set on the module and the compressor performance is controlled by an
external voltage 0-10V. Press the ENTER key to enter the setting menu, and select the menu
for setting the target value in the cooling mode.
Settings
Goal C
After opening this menu:
Goal C
+xx.x
The set value is displayed. You can use the ▼/▲ keys to set the selected digit. After you
press the ENTER key, you can change the sign. If you next press the ENTER key, you can
set other digits. Long press the ENTER key to save the settings.
Saved OK
+yy.y
Then the display returns one level back in the menu. When attempting to write lower than the
permitted value, the error message Err.min appears on the first line of the display and the
minimum permitted value of the set parameter is displayed on the second line. Similarly,
when attempting to write higher than the permitted value, the error message Err.max
appears on the first line of the display and the maximum permitted value of the set parameter
is displayed on the second line.

4.3. Setting the Desired Temperature in the Heating Mode

In the heating mode (i.e. when you select the Reg. T+ or Reg.Tx function), this menu allows
you to set the value of the output temperature in the range of −10.0ºC to +55.0ºC; the preset
temperature is +25°C. Press the ENTER key to enter the setting menu, and select the menu
for setting the target value in the heating mode.
Settings
Goal H
After opening this menu:
Goal H
+xx.x
The set value is displayed. You can change and save the desired temperature in the heating
mode in the same way as when setting the desired temperature in the cooling mode.
Saved OK
+yy.y