Daikin FXZQ-MVE Introduction Manual page 33

Table of Contents

Advertisement

7
Selection procedure
7-2
Capacity correction ratio
1
7-2-4
RXYQ12,14,24,36MY1B
7
Rate of change in cooling capacity
NOTES
1
These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum)
under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2
With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3
Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4
When overall equivalent pipe length is 90m or more, the diameter of the main liquid pipes (outdoor unit-branch sections) must be increased.
Diameter of above case
Model
RXYQ12,14MY1B
RXYQ24MY1B
Not Increased
RXYQ36MY1B
5
When the main sections of the interunit liquid pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
Equivalent lenght
80 m
Size increase
Outdoor unit
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
EXPLANATION OF SYMBOLS
H
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
p
H
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
M
L
: Equivalent pipe length (m)
α
: Capacity correction factor
Diameter of gas pipes
Model
RXYQ12,14MY1B
RXYQ24MY1B
RXYQ36MY1B
32
• Introduction
gas
liquid
ø 15.9
ø 19.1
ø 22.2
Equivalent lenght
40 m
Indoor unit
Branch
= 0m is thus approximately 1.0
p
gas
liquid
ø 28.6
ø 12.7
ø 34.9
ø 15.9
ø 41.3
ø 19.1