Checking the bus parameters
HW Config checks whether the bus parameters have to be changed when you add a new FF
device. If changes are required, the message "Change bus parameters" will be displayed. You
can then decide if you want to change the bus parameters.
● Changing bus parameters: No
● Changing bus parameters: Yes
You can find additional information on this in the following sections:
● Section "Bus parameters (Page 34)"
● Section "How to set the bus parameters (Page 39)"
Additional information
● Manufacturer information of the FF device.
● Section "How to assign parameters of the FF devices (Page 33)"
● Section "Nodes in the FOUNDATION Fieldbus (Page 17)"
● Section "How to configure FF internal interconnections (Control in the field) (Page 31)"
4.2.2

Additional notes on configuration

Device-specific number of interconnections
The number of interconnections available as Backup Link Master for an FF device is device-
specific.
Make sure that you do not exceed the permitted number of interconnections at the FF segment
during configuration. The configured interconnections are added:
● Interconnections with the process image
● CiF interconnections
FOUNDATION Fieldbus
Commissioning Manual, 03/2013, A5E03880935-02
– The new FF device will not be transferred.
The bus parameters will be changed on all FF devices and will be marked as "for download"
in the project. The following bus parameters are affected:
– Slot Time
– Maximum Response Delay
– Minimum Inter DLPDU Delay
– Makrozyklus
Note
Checking the macro cycle
Check the settings of the macro cycle.
SIMATIC; SIMATIC PDM documentation; chapter "Working with the LifeList"