Rheem 64DV Troubleshooting Manual page 70

For mid & high efficiency platforms. tankless gas
Hide thumbs Also See for 64DV:
Table of Contents

Advertisement

S V C 8 2 0 ( P ) P o c k e t M a n u a l P a g e
In 10 second intervals, cycle
unit 3 times by turning unit:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in
maintenance mode indicate
presence of flame while unit
has been off >5 seconds?
Disconnect wires at flame
rod(s). While viewing burner
chamber through sight glass:
In 10 second intervals, cycle
unit 3 times by turning unit:
ON-OFF; ON-OFF; ON-OFF
Does 0Y status in
maintenance mode indicate
presence of flame while unit
has been off >5 seconds?
Replace control board.
On remote control, go to maintenance mode 0Y table.
For maintenance mode instructions go to page 21.
All maintenance mode '0Y' readings should be done
immediately after turning the unit OFF.
IF Flame Rod(s) is detecting flame, maintenance mode will
NO
display:
Indoor Units: 05
Outdoor Units: 01
Follow maintenance mode
instructions at bottom of
page & continue to
diagnostics on next page.
Clean flame rod(s).
IF 51 – Error Code appears
after cleaning flame rod(s):
Replace flame rod(s).
69
69