4 Air Temperature Probe Offset

As standard, the air temperature probe is located on the door frame, inside the walk-in. The WIMS 100 will
display the air temperature at that particular location ONLY. However, WIMS 100 can be adjusted to estimate
the temperature of a remote location inside the walk-in.
4.1

Calculating the Probe Temperature Offset

 Establish the location inside the walk-in where you want to monitor the air temperature. Ex: Return Air
Temperature (behind the evaporator)
 Using a calibrated thermometer, measure the air temperature at that particular location. T
 Read the air temperature on the display of WIMS 100. T
 The temperature difference between the two temperatures is the temperature offset. T
Ex:
Return Air Temperature (measured behind the evaporator)
WIMS 100 Displayed Temperature
The Temperature Offset will be: (37
4.2

Adjust the Probe Temperature Offset

Make sure the controller is in "OFF" state.
If it is not, press and hold
Press and hold
To enter the default access code, press the following buttons in order:
When finished, press
Press
or
When finished, press
0
F) - (40
for 5 seconds.
for ten seconds.
.
to change the displayed unit of temperature.
.
WIMS 100
0
37
F
0
40
F
0
0
F) = -3
F
The display will show:
The display will show:
The display will show:
The display will show:
PROGRAMMING
MEASURED
OFFSET
.
9