SERVICE MENU
IN LET AIR H O T
LIMIT 35
BACK
SELECT
SERVICE MENU
INL ET AIR C O LD
LIMIT 13
BACK
SELECT
SERVICE MENU
W AS TE AIR C OLD
LIM IT 5
BACK
SELECT
SERVICE MENU
A FT E R C OO LER
NOT IN USE
BACK
SELECT
SERVICE MENU
P RE H EA T ER
NOT IN USE
BACK
SELECT
SERVICE MENU
R A DIA T OR R ET U RN
M IN T EM P . 5
BACK
SELECT
SERVICE MENU
A FT ER H EAT E R
ELE C T RIC
BACK
SELECT
SERVICE MENU
IN LET TE M P.
20
S ET PO INT
7
BACK
SELECT
SERVICE MENU
PR .C OM P .T IM E
30
PR .C OM P .LEV EL
3
BACK
SELECT
SERVICE MENU
B OO ST.TIM E
5
B OO ST. LEVE L
3
BACK
SELECT
SERVICE MENU
E C -SP EED S
BACK
SELECT
SERVICE MENU
INLE T FA N S P.
2
E XH .F AN D IF F
0
BACK
SELECT
Inlet air heating temperature 30...40c
Inlet air cooling temperature 10...15c
Freeze-alert settings 0-10c
Anti-freeze applianc e's control
Pre-heating activation
Regulation of VKL-appliance's water battery backup-sensor
Set values 0 and 5...10c, O – deactivated
Afterheating selection ELECTRICITY or WATER
Regulation of Inlet Air and Pre-heating value
The value of pre-heating should be regulated to be approx 5c higher than the
limit of cold exhaust air
Overpressure duration specification 5...20min
Overpressure limit regulation 1...4 (inlet air impeller higher than outlet air impeller)
Intensification time settings 5...120min
Intensification limit settings 1...4 (the air impellers higher than basic speed)
Speed control of the fans.
There are five fan speed modes which can be adjusted
individually within the range of 20-100%.
Running speed difference of inlet and outlet air impellers
0 Air impellers working simultaneously
-1 Inlet air impeller runs 1 step faster than the outlet air impeller
1 outlet air impeller runs 1 step faster than the inlet air impeller
ATTENTION! If air impellers run on different speed, appliance has 4 basic speeds