ABB SACE Emax 2 Series Instructions For Use Manual page 19

Low voltage air circuit-breakers
Table of Contents

Advertisement

Continued from the previous page
The following table summarises the additional functions combined with protections S2 and D:
ABB
ANSI
Threshold
(4)
S2
I5
= 0.6...10 In
-
startup
(Startup)
step = 0.1 In
S2
68
-
(Sdz)
D
I7
= 0.6...10 In
-
startup
(Startup)
step = 0.1 In
D
68
-
(SdZ)
(1)
Calculation of t
is valid for values exceeding the tripping threshold of the protection.
t
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
For the startup functions, the specified time is the period during which the protection with the different threshold remains active, calculated from the
moment the startup threshold is exceeded.
(4)
ANSI / IEEE C37-2 encoding.
(5)
Valid tolerance for frequencies in the range: fn ± 2 %. For frequency outside the range a tolerance of ± 5 % applies.
17 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Threshold
Time
tolerance
(2)
± 7 % with If ≤ 6 In
t5
startup
± 10 % with If > 6 In
step = 0.01 s
t2
= 0.04...0.2 s
-
sdz
step = 0.01 s
t7
± 10 %
startup
step = 0.01 s
t7
-
SdZ
step = 0.01 s
Calculation
(3)
formula t
= 0.1...30 s
t
= t5
t
startup
-
= 0.1...30 s
t
= t7
t
startup
= 0.1...0.8 s
-
ABB | SACE Emax 2
Tolerance t
(1)
t
The better of the two
values:
± 10 % or ± 40 ms
-
The better of the two
values:
± 10 % or ± 40 ms
-
Ekip Touch protection trip unit | 8 - Hi-Touch protections