Maersk Container Industry Star Cool SCI-20 Operating And Service Manual page 54

Refrigeration unit
Hide thumbs Also See for Star Cool SCI-20:
Table of Contents

Advertisement

53 of 112 pages
F02 Software version viewing
Function:
Viewing of software version and revision.
Value:
-
F03 Compressor FC type setting
Function:
Setting of actual FC type.
Value:
Setting as DANFOSS for Danfoss VLT
and NONE for no FC mounted (see "22. Emergency opera-
tion" p. 92).
F04 Compressor frequency converter ID
Function:
Viewing of ID for FC for compressor.
Value:
-
F05 Setting of phase direction
Function:
Setting of phase direction.
Value:
Is only possible when AL423 is active. Default setting is AUTO for automatic phase detection -
automatically selected when the unit has been switched off for more than 30 min. before switching
it on again. Can be used for manual phase setting: Setting as CW for clockwise rotation or CCW for
counter-clockwise rotation. If manual phase direction is set, heat is reduced to 60% of max.
F06 Calibration of air exchange sensor
Function:
Zero adjust of air exchange sensor when the air inlet is closed.
Value:
Actual value of sensor is set to zero when Enter key
is pressed.
F07 Type of low pressure transmitter
Function:
Set the pressure transmitter that is physically mounted for low pressure measurement. Press En-
ter for 3 sec. to make the selection.
Value:
Select between AKS, NSK or DST.
F08 Type of high pressure transmitter
Function:
Set the pressure transmitter that is physically mounted for high pressure measurement. Press
Enter for 3 sec. to make the selection.
Value:
Select between AKS, NSK or DST.
F09 Valve type
Function:
Set the valve type to correspond to physical mounted type.
Value:
R134a only, R134a/R513A.
Operating and service manual