4.4

IP address

The IP address can be set using four different procedures, and these will be described in more detail below.
Procedure
Explanation
KS2000
Addressing using the KS2000 configuration
software and DIP switches
ARP
Addressing via the ARP table [} 24]
BootP
Addressing via BootP server [} 25]
DHCP
Addressing via DHCP server
4.4.1

Configuration with KS2000

The KS2000 configuration software (from version 3.2.8) can be used to set the TCP/IP address in a dialog
box, or it can be written directly into the registers. DIP switches 9 and 10 (for BK9050 DIP switches 1 and 2
in blue) should both be OFF (0) before switching on.
Table 100
Register
0
1
Default
Byte
1
2
3
4
Sample
Fig. 7: DIP switch
Switch no.
1
Valence
1
In this example ON
Value
1
Software reset
A software reset is required to save changes in the Bus Coupler tables. A hardware reset (power
on/off) is not sufficient!
BK9055 and BK9105
High-Byte
IP-Byte 2
Not used
Default value (hex)
0xAC
0x10
0x11
(DIP switch)
2
3
4
5
2
4
8
16
OFF
OFF ON
OFF
0
0
8
0
Version: 2.0.0
Parametrization and commissioning
Necessary components
KS2000 configuration software and KS2000
cable
PC with network
BootP server
DHCP server
Low-Byte
IP-Byte 1
IP-Byte 3
Default value (dec)
172
dec
16
dec
17
dec
(0 to 255
dec
6
7
8
9
32
64
128
-
OFF
ON
ON
OFF
0
64
128
-
)
10
-
OFF
-
Total=201