8
Operations Count (U10) Signal
9
Auto Inhibit Terminal Block Input
10
VRC1 contacts
11
VRC2 contacts
12
Remote Switch position
13
Manual Switch position
14
Auto Inhibit Out Status
Binary Outputs
Point #
Description
0
Tap Raise
1
Tap Lower
2
Auto Inhibit (Latch On/Off)
Analog Inputs
Point #
Description
0
Op Count Last Year
1
N/A
2
R/A/M switch position
3
Power Flow Direction Indicator
4
VRC contacts status
5
Band, VRC, VLC status
6
Tap Position
7
Load Current
8
Load Voltage
9
Load Voltage (primary)
10
Source Voltage
11
Source Voltage (primary)
12
KVA
13
KVAR
14
KW
15
Power Factor
Analog Outputs
Point #
Description
0
Op Count Total

6.2.5 Simple

Binary Inputs
Point #
Description
0
Auto Inhibit Status
1
Remote Switch position
2
Manual Switch position
Binary Outputs
Point #
Description
0
Tap Raise
1
Tap Lower
2
Auto Inhibit (On/Off)
Analog Inputs
Point #
Description
0
Tap Position
1
Load Voltage
2
Load Current
3
Source Voltage
Analog Outputs
18