Metering - Siemens MJ-5 Installation Manual

Communications module, fiber optic and rs-232/485/ network
Hide thumbs Also See for MJ-5:
Table of Contents

Advertisement

No Analog Outputs in the Simple set currently.

6.2.6 Metering

Binary Inputs
Point #
Description
0
LOW Voltage Limiting, [1=On]
1
HIGH Voltage Limiting, [1=On]
2
Automatic Operation, [1=Inhibited]
3
Power Flow Direction, [0=Fwd, 1=Rev]
4
R/A/M Switch, [0=Off/Manual, 1=Auto/Remote]
5
Voltage Reduction Input 1, [0=Open, 1=Closed]
6
Voltage Reduction Input 2, [0=Open, 1=Closed]
7
Supervisory Switch, [0=Off, 1=On (Remote)]
8
Neutral Position Status, [0=inactive, 1=active]
9
Low Battery Status, [0=inactive, 1=active]
10
Raise Limit Reached, [0=inactive, 1=active]
11
Lower Limit Reached, [0=inactive, 1=active]
Binary Outputs
Point #
Description
0
Control Raise (1=raise)
1
Control Lower (1=lower)
2
Remote Auto/Manual (1=block)
3
Fwd Voltage Level (+/-.1V) (0=dec, 1=inc)
4
Bandwidth Voltage (+/-.1V) (0=dec, 1=inc)
5
Fwd Time Delay (+/- 5s) (0=dec, 1=inc)
6
Fwd Reactive Comp (+/- 1V) (0=dec, 1=inc)
7
Local Voltage Reduct (1=Active)
8
Remote Volt Reduct (1=Active)
9
Local Volt Reduct % (+/-.5V) (0=dec, 1=inc)
10
Remote Volt Red. % (+/-.5V) (0=dec, 1=inc)
11
Fwd Resistive Comp (+/- 1V) (0=dec, 1=inc)
12
Reset Demands & min/max (AI 20-26)
13
Reset Energies (AI 27-28)
Analog Inputs
Point #
Description
0
Operations Counter (100's)
1
Operations Counter (10's and 1's)
2
kVA Load
3
kW Load
4
Hardware Status (0=All Good)
5
Primary Load Current in Amps
6
Secondary Load Voltage
7
Primary Load Voltage
8
Primary Source Voltage
9
kVAR Load
10
Power Factor
11
Compensated Voltage (Sec.)
12
% Voltage Reduction in Effect
13
Tap Position
14
Voltage Reduction Status
15
Voltage Limit Status
16
Tap Control Mode Status
17
R/A/M switch position
MJ-5 Communications Module