SMP1400/2000/2500/3500EILCD
User's Manual

IMPORTANT SAFETY INFORMATION

(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to unpack,
install, or operate the Static UPS.
Insure the wall outlet and Static UPS are located near the equipment being attached for proper
accessibility.
To reduce risk of damage and injury, please use batteries with good quality.
Provide adequate ventilation for the battery compartment. The battery enclosure should be designed to
prevent accumulation and concentration of hydrogen gas at the top of the compartment.
DO NOT expose the Static UPS to rain, snow or liquids of any type. The Static UPS is designed for
indoor use only.
DO NOT obstruct the ventilation openings.
DO NOT connect neutral of the power distribution box on the wall to the output neutral of Static
UPS. Otherwise the reversed polarity will damage the Static UPS and the connected equipment.
CAUTION! Risk of electric shock, do not remove cover. No user serviceable parts inside.
The battery can energize hazardous live parts inside even when the AC input power is disconnected.
To avoid electrical shock, turn off the Static UPS and unplug it from the AC power source before
servicing the battery. Servicing the battery can only be performed by trained personnel.
INSTALLING YOUR STATIC UPS SYSTEM
UNPACKING
Inspect the Static UPS upon receipt. The box should contain the following:
SMP1400/2000EILCD:
(1) Static UPS Unit 1; (2) User Manual 1; (3) Battery Cable
(5) Terminal Splices
6 (using for the wire connection on input/output terminal)
SMP2500/3500EILCD:
(1) Static UPS Unit 1; (2) User Manual 1; (3) Battery Cable
OVERVIEW
The SMP1400/2000/ 2500/ 3500EILCD provides battery backup during power outages. The
SMP1400/2000/ 2500/ 3500EILCD ensures consistent power to your computer system and its included
software will automatically save your open files and shut down your computer system during a utility
power loss.
HARDWARE INSTALLATION GUIDE
Before installation, please read and understand the following instructions:
1.
Placement
The Static UPS must be installed in a protected environment away from heat- emitting appliances
such as a radiator or heat register. Do not install this product where excessive moisture is present.
2.
Ventilation
The location should provide adequate air flow around the Static UPS with 10 CM minimum
clearance on all sides for proper ventilation.
3.
Connect the Battery
Connect the external battery with the DC cables from the back of the Static UPS. Follow battery
polarity guide located near battery cables as below.
"+" Red cable for battery positive polarity;
"-" Black cable for battery negative polarity.
4.
Connect to AC and Charge the Battery
Connect the Static UPS to a wall outlet. Avoid using extension cords and adapter plugs. Charging
the battery for at least 8 hours is recommended to insure that the battery is fully charged. To
recharge the battery, simply leave the unit plugged into a wall outlet. To maintain optimal battery
charge, leave the Static UPS plugged into an AC outlet at all times.
This Static UPS can be charged even when Static UPS is not turned on.
5.
Connect the Load
Connect the equipment to the Static UPS outlet. Please make sure that the total loads of your
equipments are less than the maximum total power load of the Static UPS. Connect your computer,
monitor, and any externally-powered data storage device (Hard drive, Tape drive, etc.) into the
outlets only when the Static UPS is off and unplugged. Do not plug a laser printer, copier, space
heater, vacuum, paper shredder or other large electrical device into The Static UPS. The power
demands of these devices will overload and possibly damage the unit.
K01-C000226-01
1; (4) Warranty card 1;
3; (4) Warranty card 1

BASIC OPERATION

FRONT PANEL DESCRIPTION
SMP1400/2000EILCD
1.
LCD Display
The LCD will display the Static UPS status including input voltage, output voltage, percentage of
load and battery, etc.
2.
Power On/Off Button
Press the power Button to turn the Static UPS ON or OFF.
3.
LCD Display Button
a. GENERAL MODE:
The Button can be used to select the LCD display contents Including input/output voltage, etc.
b. SET-UP MODE:
Step1: Hold the display button for 9 seconds to enter set-up Mode, the icons
OUTPUT
And
keep lighting.
Step2: By pressing the display Button, users can switch between two setup pages. User
configurable functions are as follows:
Set-up page
Item
1
Mode setting
2
Charge setting
Step3: Press and hold the display button for 4 seconds .When the characters blink, the value of
each item can be changed by slighting pressing the function select button
Step4: Press and hold the display button for 4 seconds again to save the value and exit the present
set-up page
Step5:To save the value and return to general mode, press the display button for 9 seconds
NOTE: If the machine is left idle for over 30 seconds during setup, it will return to general
mode without saving changes automatically
REAR PANEL DESCRIPTION
SMP1400/2000EILCD SMP2500/ 3500EILCD
1.
Input/ Output Terminal Block
Connect the AC Power to Static UPS./ Connect to your equipment.
The Static UPS provides outlets for connected equipment to insure temporary uninterrupted
operation during a power failure and against surges and spikes.
2.
Input Circuit Breaker
The circuit breaker provides optimal overload protection.
3.
Serial Port to PC
This port allows connection and communicates from the DB-9 serial on the computer to the Static
UPS unit. The Static UPS communicates its status to the PPBE software.
4.
DC Input Cable(Black "-")
Connect to battery negative polarity.
5.
DC Input Cable (Red "+")
Connect to battery positive polarity.

FUNCTIONAL TEST

AC Mode
The Static UPS delivers power to the load derived from the utility and maintains proper battery charge.
On-Battery Mode
The Static UPS operates on battery when the utility voltage has fallen outside the limits. Local users are
alerted to this mode of operation by visual and audible indicators. The Static UPS provides power to the
load from the battery and the output voltage of the Static UPS are regulated within a narrow range
1.
Button On
Press the power Button 2 seconds then the status LCD will light up.
2.
Button Off
Press the power Button 2 seconds again, the status LCD will go off.
3.
Cold Start / Start on Battery:
This Static UPS can be turned on even when AC is not present.
Press the power Button 2 seconds then the status LCD will light up.
SMP2500/ 3500EILCD
INPUT
Icon
Character
Value
Inverter mode(default)
UPS mode
Battery capacity:
65-150AH(default)
Battery capacity:
150-300AH

Advertisement

loading

Summary of Contents for CyberPower SMP1400EILCD

  • Page 1: Basic Operation

    BASIC OPERATION FRONT PANEL DESCRIPTION SMP1400/2000/2500/3500EILCD User’s Manual K01-C000226-01 SMP1400/2000EILCD SMP2500/ 3500EILCD LCD Display IMPORTANT SAFETY INFORMATION The LCD will display the Static UPS status including input voltage, output voltage, percentage of load and battery, etc. Power On/Off Button (SAVE THESE INSTRUCTIONS) Press the power Button to turn the Static UPS ON or OFF.