Differential for temperature
dAH
1.0
Pr2
alarm (defrost probe)
Temperature alarm delay
ddA
15
Pr2
(defrost probe)
High temperature alarm setting
FLU
150
Pr2
(fan probe)
Low temperature alarm setting
FLL
-55
Pr2
(fan probe)
Differential for temperature
FAH
1.0
Pr2
alarm (fan probe)
Temperature alarm delay (fan
FAd
15
Pr2
probe)
Delay of temperature alarm at
dAo
1.3
Pr1
start-up
Alarm delay at the end of
EdA
30
Pr1
defrost
Temperature alarm exclusion
dot
Pr1
15
after door open
Sti
1.3
Pr2
Stop regulation interval
Std
3
Pr2
Stop duration
Modulating output configuration
oA7
Pr2
ALr
(if CoM=oA7)
CoM
Cur
Pr2
Modulating output configuration
Digital
Inputs
i1P
Pr1
cL
Digital input 1 polarity
i1F
dor
Pr1
Digital input 1 configuration
d1d
15
Pr1
Digital input 1 activation delay
i2P
cL
Pr1
Digital input 2 polarity
i2F
LiG
Pr1
Digital input 2 configuration
d2d
Pr1
5
Digital input 2 activation delay
Number of pressure switch
nPS
15
Pr1
activation before lock
Compressor and fan status
OdC
F-C
Pr1
when open door
Outputs restart after door open
rrd
30
Pr1
alarm
Clock
CbP
Y
Pr1
Clock presence
Hur
- - -
Pr1
Current hour
Min
- - -
Pr1
Current minutes
dAY
- - -
Pr1
Current day
Hd1
nu
Pr1
First weekly day
Hd2
nu
Second weekly day
Pr1
Hd3
nu
Pr1
Third weekly day
Energy saving cycle start during
ILE
0.0
Pr1
workdays
Energy saving cycle length
dLE
0.0
Pr1
during workdays
Energy saving cycle start during
ISE
0.0
Pr1
holidays
Energy saving cycle length
dSE
0.0
Pr1
during holidays
Temperature increasing during
HES
0.0
Pr1
Energy Saving cycle
Ld1
nu
Pr1
Workdays First defrost start
Ld2
nu
Pr1
Workdays Second defrost start
Ld3
nu
Pr1
Workdays Third defrost start
Ld4
nu
Pr1
Workdays Fourth defrost start
Ld5
nu
Pr1
Workdays Fifth defrost start
Ld6
nu
Pr1
Workdays Sixth defrost start
Sd1
nu
Pr1
Holidays First defrost start
Sd2
nu
Pr1
Holidays Second defrost start
Sd3
nu
Pr1
Holidays Third defrost start
Sd4
nu
Pr1
Holidays Fourth defrost start
Sd5
nu
Pr1
Holidays Fifth defrost start
1592023020 XM660K_XM669K GB r1.0 07.01.2013.doc
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
Energy Saving
0 ÷ 255 (min.)
FLL ÷ 150.0° or FLL ÷ 302°F
HES
-55,0°C ÷ FLU or -67°F ÷ FLU
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
L.A.N. Management
0 ÷ 255 (min.)
LMd
0 ÷ 24.0(144)
(hours.10min)
dEM
0 ÷ 255 min
0 ÷ 255 min
"nu"(0) ÷ 24.0(144)
(hour.10min)
1 ÷ 255 min
CPr(0) - dEF(1) - FAn(2) -
ALr(3) - LiG(4) - AUS(5) -
db(6) - OnF(7)
CUr(0) - tEn(1) - PM5(2) -
PM6(3) - oA7(4)
OP(0) - CL(1)
Probe Configurations
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
0 ÷ 255 (min.)
OP(0) - CL(1)
EAL(0) - bAL(1) - PAL(2) -
dor(3) - dEF(4) - AUS(5) -
LiG(6) - OnF(7) - Htr(8) -
FHU(9) - ES(10) - Hdy(11)
0 ÷ 255 (min.)
0 ÷ 15
no(0) - FAn(1) - CPr(2) - F-
C(3)
0 ÷ 255 (min.)
n(0) – Y(1)
- - -
Service
- - -
Sun(0) - SAt(6)
Sun(0) - SAt(6) - nu(7)
Sun(0) - SAt(6) - nu(7)
Sun(0) - SAt(6) - nu(7)
0 - 23.5(143) (hours.10min)
0 ÷ 24.0(144)
(hours.10min)
0 - 23.5(143) (hours.10min)
0 ÷ 24.0(144)
(hours.10min)
[-30.0°C ÷ 30.0°C] [-54°F ÷
54°F]
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld1 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld2 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld3 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld4 ÷ 23.5(143) - nu(144)
(hours.10min)
Ld5 ÷ 23.5(143) - nu(144)
(hours.10min)
0.0 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd1 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd2 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd3 ÷ 23.5(143) - nu(144)
(hours.10min)
Sd4 ÷ 23.5(143) - nu(144)
(hours.10min)
XM660K - XM669K
Sd6
nu
Pr1
Holidays Sixth defrost start
ESP
P1
Pr1
Energy saving probe selection
Temperature increasing during
Pr1
0.0
Energy Saving
Energy saving activation when
PEL
n
Pr1
Light switched off
y
Pr2
Defrost Synchronisation
y
Pr2
Defrost end Synchronisation
LSP
n
Pr2
SET-POINT Synchronisation
Display Synchronisation
LdS
n
Pr2
(temperature sent via LAN)
LOF
n
Pr2
ON/OFF Synchronisation
LLi
y
Pr2
Light Synchronisation
LES
n
Pr2
Energy Saving Synchronisation
LSd
n
Pr2
Remote probe displaying
LPP
n
Pr2
Pressure value sent in LAN
Cooling request from LAN
StM
n
Pr2
enable compressor relay
P1C
NtC
Pr2
P1 configuration
ot
0.0
Pr2
P1 calibration
P2C
NtC
Pr2
P2 configuration
oE
Pr2
0.0
P2 calibration
P3C
NtC
Pr2
P3 configuration
o3
0.0
Pr2
P3 calibration
P4C
NtC
Pr2
P4 configuration
o4
Pr2
0.0
P4 calibration
P5C
420
Pr2
P5 configuration
o5
0.0
Pr2
P5 calibration
P6C
PtM
Pr2
P6 configuration
o6
0.0
Pr2
P6 calibration
CLt
- - -
Pr1
ON/OFF percentage (C.R.O.)
Time remaining before next
tMd
- - -
Pr1
defrost activation (only for
interval defrost)
LSn
- - -
Pr1
Number of devices in LAN
LAn
- - -
Pr1
List of address of LAN devices
Other
Adr
1
Pr1
Modbus address
rEL
- - -
Pr1
Firmware release
Ptb
- - -
Pr1
Parameter table
Pr2
- - -
Pr1
PR2 menu access
Sd5 ÷ 23.5(143) - nu(144)
(hours.10min)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - tEr(6)
[-30.0°C ÷ 30.0°C] [-54°F ÷
54°F]
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
n(0) – Y(1)
nP(0) - Ptc(1) - ntc(2) - PtM(3)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
nP(0) - Ptc(1) - ntc(2) - PtM(3)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
nP(0) - Ptc(1) - ntc(2) - PtM(3)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
nP(0) - Ptc(1) - ntc(2) - PtM(3)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
nP(0) - Ptc(1) - ntc(2) - PtM(3)
- 420(4) - 5Vr(5)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
nP(0) - Ptc(1) - ntc(2) - PtM(3)
[-12,0°C ÷ 12,0°C] [-21°F ÷
21°F]
(read only)
(read only)
1 ÷ 8 (read only)
1 ÷ 247 (read only)
1 ÷ 247
(read only)
(read only)
(read only)
8/8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dixell xm660k

Table of Contents