Emerson Dixell XM669K Installing And Operating Instructions page 7

Controllers for multiplexed cabinets
Table of Contents

Advertisement

CCS
2.0
Pr2
Continuous cycle set point
Compressor ON time with faulty
Con
15
Pr2
probe
Compressor OFF time with
CoF
30
Pr2
faulty probe
Measurement unit: Celsius ,
CF
°C
Pr2
Fahrenheit
PrU
Pr2
rE
Pressure Mode
PMU
bAr
Pr2
Pressure measurement unit
Pressure displaying mode:
PMd
PrE
Pr2
temperature or pressure
Resolution (only °C) : decimal,
rES
dE
Pr2
integer
Lod
P1
Pr2
Local display: default display
rEd
P1
Pr2
Remote display: default display
dLy
0
Pr1
Display delay
rPA
P1
Pr1
Regulation probe A
rPb
nP
Pr1
Regulation probe B
Virtual probe percentage (room
rPE
Pr1
100
temperature)
Electronic Expansion Valve
Fty
404
Pr1
Kind of gas
SSH
8.0
Pr1
Superheat set point
CyP
6
Pr1
Cycle Period
Proportional band for superheat
Pb
5.0
Pr1
regulator
Band Offset for superheat
rS
0.0
Pr1
regulator
Integration time for superheat
inC
120
Pr1
regulator
PEO
50
Pr1
Probe error opening percentage
Probe error delay before
PEd
On
Pr1
stopping regulation
OPE
85
Pr1
Start opening percentage
SFd
1.3
Pr1
Start function duration
Opening percentage after
OPd
100
Pr1
defrost phase
Pdd
Pr1
1.3
Post defrost function duration
Maximum opening percentage
MnF
100
Pr1
at normale functioning
Delay before stopping valve
dCL
Pr1
0
regulation
Fot
nu
Pr1
Forced opening percentage
tPP
PP
Pr2
Type of pressure transducer
PA4
-0.5
Pr2
Probe value at 4 mA or at 0V
P20
11.0
Pr2
Probe value at 20 mA or at 5V
Lower pressure limit for
LPL
-0.5
Pr1
superheat regulation
Maximum operating pressure
MOP
11.0
Pr1
threshold
Lowest operating pressure
LOP
-0.5
Pr1
threshold
Delta MOP-LOP opening
dML
30
Pr1
variation
Maximum superheat alarm
MSH
Pr1
80.0
threshold
Minimum superheat alarm
LSH
1.0
Pr1
threshold
SHy
0.5
Pr1
Superheat alarm hysteresis
Superheat alarm activation
SHd
3.0
Pr1
delay
FrC
100
Pr1
Fast-recovery costant
Defrost
dPA
P2
Pr1
Defrost probe A
1592023020 XM660K_XM669K GB r1.0 07.01.2013.doc
[-55.0°C ÷ 150,0°C] [-67°F ÷
dPb
302°F]
dPE
0 ÷ 255 (min.)
0 ÷ 255 (min.)
EdF
°C(0) - °F(1)
rE(0) - Ab(1)
bAr(0) – PSI(1) - MPA(2)
Hyr
tEM(0) - PrE(1)
dE(0) - in(1)
nP(0) - P1(1) - P2(2) - P3(3) -
ddP
P4(4) - P5(5) - P6(6) – tEr(7) -
dEF(8)
d2P
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - P6(6) – tEr(7) -
dEF(8)
0 ÷ 24.0(144) (Min.10s)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
MdF
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
dSd
0 ÷ 100 (100=rPA, 0=rPb)
dFd
dAd
R22(0) - 134(1) - 404(2) -
407(3) - 410(4) - 507(5) -
CO2(6)
dPo
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
dAF
1 ÷ 15 s
[0.1°C ÷ 60.0 °C] [1°F ÷ 108
Fan
°F]
[-12.0°C ÷ 12.0°C] [-12°C ÷
FPA
12°C] [-21°F ÷ 21°F]
FPb
0 ÷ 255 s
FPE
0 ÷ 100
FnC
0 ÷ 239 s - On(240)
0 ÷ 100
Fnd
0 ÷ 42.0(252) (min.10sec)
FCt
0 ÷ 100
0 ÷ 42.0(252) (min.10sec)
FHy
0 ÷ 100
Fod
0 ÷ 255 s
Fon
0 ÷ 100 - "nu"(101)
FoF
PP(0) - LAN(1)
BAR : [PrM=rEL] -1.0 ÷ P20
SOA
[PRM=Abs] 0.0 ÷ P20
PSI : [PrM=rEL] -14 ÷ P20
SdP
[PRM=Abs] 0 ÷ P20
dKP : [PrM=rEL] -10 ÷ P20
ASr
[PRM=Abs] 0 ÷ P20
BAR : [PrM=rEL] PA4 ÷ 50.0
PbA
[PrM=AbS] PA4 ÷ 50.0
PSI :
[PrM=rEL] PA4 ÷ 725
AMi
[PrM=AbS] PA4 ÷ 725
dKP : [PrM=rEL] PA4 ÷ 500
AMA
[PrM=AbS] PA4 ÷ 500
PA4 ÷ P20
AMt
LOP ÷ P20
Alarm
PA4 ÷ MOP
rAL
0 ÷ 100
ALC
[LSH ÷ 80,0°C]
[LSH ÷
144°F]
ALU
[0.0 ÷ MSH °C]
[0 ÷ MSH
°F]
ALL
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 42.0(252) (min.10sec)
AHy
0 ÷ 100
ALd
dLU
nP(0) - P1(1) - P2(2) - P3(3) -
dLL
P4(4) - P5(5)
XM660K - XM669K
nP
Pr1
Defrost probe B
Virtual probe percentage
100
Pr1
(defrost temperature)
tdF
EL
Pr1
Defrost type
(Only for model with RTC)
Pr1
in
Defrost mode: Clock or interval
Srt
150
Pr1
Heater set point during defrost
2.0
Pr1
Differential for heater
tod
255
Pr1
Time out for heater
Minimum temperature
dtP
Pr1
0.1
difference to start defrost
60
Pr1
Delay before starting defrost
n
Pr1
Defrost with two probes
Defrost termination temperature
dtE
8.0
Pr1
(Probe A)
Defrost termination temperature
dtS
Pr1
8.0
(Probe B)
idF
6
Pr1
Interval between defrosts
30
Pr1
Defrost Maximum duration
0
Pr1
Start defrost delay
it
Pr1
Display during defrost
30
Pr1
Defrost display time out
Fdt
0
Pr1
Drain down time
n
Pr1
Defrost at start-up
Defrost delay after continuous
0.0
Pr1
cycle
P2
Pr1
Fan probe A
nP
Pr1
Fan probe B
Virtual probe percentage (fan
Pr1
100
management)
O-n
Pr1
Fan operating mode
10
Pr1
Fan delay after defrost
Temperature differential to
10
Pr1
avoid short cycles of fans
FSt
2.0
Pr1
Fan stop temperature
1.0
Pr1
Fan stop differential
Fan activation time after defrost
0
Pr1
(without compressor)
0
Pr1
Fan ON time
0
Pr1
Fan OFF time
Kind of regulation for
trA
UAL
Pr2
modulating output
80
Pr2
Fixed speed for fan
30.0
Pr2
Default Dew Point value
Differential for fan / offset for
1.0
Pr2
anti sweat heater
Proportional band for
5.0
Pr2
modulating output
Minimum output for modulating
0
Pr2
output
Maximum output for modulating
100
Pr2
output
Time with fan at maximum
200
Pr2
speed
P1
Pr1
Probe for temperature alarm
Temperature alarm
Ab
Pr1
configuration
10
Pr1
High temperature alarm setting
-30
Pr1
Low temperature alarm setting
Differential for temperature
1.0
Pr1
alarm
15
Pr1
Temperature alarm delay
High temperature alarm setting
150
Pr2
(defrost probe)
Low temperature alarm setting
-55
Pr2
(defrost probe)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
0 ÷ 100 (100=dPA, 0=dPb)
EL(0) - in(0)
rtc(0) - in(1)
[-55.0°C ÷ 150°C] [-67°F ÷
302°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
[0.1°C ÷ 50.0°C]
[1°F ÷
90°F]
0 ÷ 60 (min.)
n(0) – Y(1)
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
0 ÷ 120 (hours)
0 ÷ 255 (min.)
0 ÷ 255 (min.)
rt(0) - it(1) - SEt(2) - dEF(3)
0 ÷ 255 (min.)
0 ÷ 255 (min.)
n(0) – Y(1)
0 ÷ 24.0(144)
(hours.10min)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5)
0 ÷ 100 (100=FPA, 0=FPb)
C-n(0) - O-n(1) - C-y(2) - O-
y(3)
0 ÷ 255 (min.)
[0.0°C ÷ 50.0°C] [0°F ÷ 90°F]
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
0÷15 (min.)
0÷15 (min.)
UAL(0) - rEG(1) - AC(2)
AMi ÷ AMA
[-55.0°C ÷ 50.0°C] [-67°F ÷
122°F]
[-25.5°C ÷ 25.5°C] [-45°F ÷
45°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ AMA
AMi ÷ 100
0 ÷ 255 s
nP(0) - P1(1) - P2(2) - P3(3) -
P4(4) - P5(5) - tEr(6)
rE(0) - Ab(1)
[0.0°C ÷ 50.0°C o ALL ÷
150.0°] [0°F ÷ 90°F o ALL ÷
302°F]
[0.0°C ÷ 50.0°C o -55,0°C ÷
ALU]
[0°F ÷ 90°F o -67°F
÷ ALU°F]
[0.1°C ÷ 25.5°C] [1°F ÷ 45°F]
0 ÷ 255 (min.)
dLL ÷ 150.0° or dLL ÷ 302°F
-55,0°C ÷ dLU or -67°F ÷ dLU
7/8