Supported - Binary Output
B.7 Supported - Binary Output
BACnet
Enumeration
0
1
2
Present Value
3
7
22
BACnet
Enumeration
0
1
2
Tracking Value
3
7
22
BACnet
Enumeration
0
Event State
1
2
BACnet
Enumeration
Reliability
0
7
BACnet
Enumeration
0
Mode
11
12
BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
BACnet
NFN State
LifeSafetyState
IssQuiet
Normal
IssPreAlarm
PreAlarm
IssAlarm
Fire Alarm, Security Alarm (Life/Property), Critical
Process Alarm, (Life/Property), Medical Emergency
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble, Fire
Device or Zone, Disabled, Non-Fire Device Disabled
IssActive
Non-Fire Activation
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's Tour)
BACnet
NFN State
LifeSafetyState
IssQuiet
Normal
IssPreAlarm
PreAlarm
IssAlarm
Fire Alarm, Security Alarm (Life/Property), Critical
Process Alarm (Life/Property), Medical Emergency
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble, Fire
Device or Zone, Disabled, Non-Fire Device Disabled
IssActive
Non-Fire Activation
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's Tour)
BACnet Event State
NFN State
EsNormal
Normal
EsFault
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fireevice Disabled, Non-Fire Device Disabled
EsOffNormal
All statuses other than normal and fault.
BACnet Reliability
NFN State
reNoFaultDetected
All statuses other than trouble.
re_UnreliableOther
Security Trouble, Fire Trouble, Non-Fire Trouble
BACnet Mode
NFN State
IsmOff
Power-Up State
IsmEnabled
Set if point has been disabled and subsequently
enabled since startup.
IsmDisabled
Fire Device or Zone Disabled, Non-Fire Device
Disabled
BACnet PIC Statement