6�1�2 Standard Diagnostic Object - IFM Electronic ecomat 300 AC1155 Device Manual

As-i / rs-485 gateway
Table of Contents

Advertisement

Read standard ID object request
Byte no.
0
1
2
Read standard ID object reply
Byte no.
0
1
2
3
4
5
6.1.2 Standard diagnostic object
Verification if the module has an error on the AS-i side or if it functions without
error�
Read standard diagnostic object request
Byte no.
0
1
2
Read standard diagnostic object reply
Byte no.
0
1
Description
Command code 16 = read standard
Index 0 = ID object
Length to be read = 5
Description
Command code 80 = read standard OK
AS-i manufacturer ID (high) = 00
AS-i manufacturer ID (low) = 04
AS-i device ID (high) = 00
AS-i device ID (low) = 65
Number of analogue AS-i inputs and outputs 09
(no outputs, 1 byte input)
Description
Command code 16 = read standard
Index 1 = ID object
Length to be read = 1
Description
Command code 80 = read standard OK
Standard diagnostic code:
00
= no error
hex
01���05 see chapter 6�5