Worcester DANESMOOR 15/19 Installation And Servicing Instructions page 4

Conventional flue and room sealed bf floor standing oil-fired pressure jet appliances
Table of Contents

Advertisement

12/14 Table 2. Electro Oil Inter B9A Burner (See Fig. 21)
Fuel
Nozzle
28 Sec. Kerosene
0.40 60°ES
28 Sec. Kerosene
0.50 60°ES
15/19 Table 3. Electro Oil Inter B9B Burner (See Fig. 21)
Fuel
Nozzle
28 Sec. Kerosene
0.50 60°ES
28 Sec. Kerosene
0.55 80°EH
28 Sec. Kerosene
0.60 60°ES
35 Sec. Gas Oil*
0.50 80°S
20/25 Table 4. Electro Oil Inter B11C Burner (See Fig. 22)
Fuel
Nozzle
28 Sec. Kerosene
0.60 80°EH
28 Sec. Kerosene
0.75 80°EH
28 Sec. Kerosene
0.75 80°EH
35 Sec. Gas Oil*
0.60 80°S
35 Sec. Gas Oil*
0.60 80°S
20/25 Table 5. Electro Oil Inter B11C Burner (See Fig. 22)
Fuel
Nozzle
28 Sec. Kerosene
0.60 80°EH
28 Sec. Kerosene
0.75 80°EH
28 Sec. Kerosene
0.75 80°EH
26/32 Table 6. Electro Oil Sterling 40 Burner (See Fig. 23)
Fuel
Nozzle
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
0.85 80°EH
28 Sec. Kerosene
1.00 80°EH
35 Sec. Gas Oil*
0.50 80°H
35 Sec. Gas Oil*
0.55 80°H
35 Sec. Gas Oil*
0.55 80°H
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
135
1.11
1.41
100
1.30
1.64
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
1.40
1.77
100
1.59
2.01
105
1.78
2.25
155
1.80
2.12
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
1.87
2.37
115
2.10
2.66
135
2.34
2.96
130
2.13
2.51
160
2.37
2.79
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
1.87
2.37
115
2.10
2.66
135
2.34
2.96
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
2.36
2.99
145
2.66
3.37
130
2.95
3.74
260
2.44
2.87
265
2.76
3.25
330
3.06
3.60
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
195
9.5
8.0
210
10.5
8.5
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
215
10.5
8.5
225
10.5
8.75
235
11.5
9.0
235
11.5
9.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
215
10.5
6.0
225
10.5
7.0
240
11.5
7.5
225
11.0
7.25
240
11.5
8.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
215
10.5-11.0
6.0
225
11.0-11.5
7.0
240
11.5-12.0
7.5
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
225
11.0-11.5
11
240
11.0-11.5
12
245
11.5-12.0
16
220
11.5-12.0
235
11.5-12.0
14
240
12.0-12.5
16
4
Appliance
Input
kW
Btu/hr
13.5
46,000
15.5
53,000
Appliance
Input
kW
Btu/hr
17
58,000
19
65,000
21.5
73,000
21.5
73,000
Conventional Flue Appliance (CF/LLD)
Appliance
Input
kW
Btu/hr
22.5
77,000
25
86,000
28
96,000
25
86,000
28
96,000
RS Balanced Flue Appliance
Appliance
Input
kW
Btu/hr
22.5
77,000
25
86,000
28
96,000
Conventional Flue Appliance (CF/LLD)
Appliance
Input
kW
Btu/hr
28.5
97,000
32
109,000
35.5
121,000
9
28.5
97,000
32
109,000
35.5
121,000
Output
kW
Btu/hr
12
41,000
14
48,000
Output
kW
Btu/hr
15
51,000
17
58,000
19
65,000
19
65,000
Output
kW
Btu/hr
20
68,000
22.5
77,000
25
85,000
22.5
77,000
25
85,000
Output
kW
Btu/hr
20
68,000
22.5
77,000
25
85,000
Output
kW
Btu/hr
26
89,000
29
99,000
32
109,000
26
89,000
29
99,000
32
109,000