Mounting Hole Location; Checkout Procedure - American Standard 4A7A5 Installer's Manual

Table of Contents

Advertisement

INSTALLER'S GUIDE
NOTE:
For model base size,
see table on page 7.
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Refrigerant Line, Leak checked ...................... [ ]
2. Suction Lines and Fittings
properly insulated ........................................... [ ]
3. Have all Refrigerant Lines been secured and
isolated properly? ........................................... [ ]
4. Have passages through masonry been
sealed? If mortar is used, prevent mortar
from coming into direct contact with
copper tubing.................................................. [ ]
5. Verify tightness of all electrical connects ........ [ ]
6. Observe outdoor fan during on cycle for
clearance and smooth operation .................... [ ]
Technical Literature - Printed in U.S.A.
American Standard Inc.
Troup Highway
Tyler, TX 75707

MOUNTING HOLE LOCATION

CHECKOUT PROCEDURE

7. Indoor coil drain line drains freely.
8. Supply registers and return grilles
9. Return air filter installed .................................. [ ]
10. Thermostat thermometer is accurate.
11. Is correct speed tap being used?
12. Operate complete system in each mode
Note: All Dimensions Are
In MM (Inches).
Pour water into drain pan ............................... [ ]
open and unobstructed ................................... [ ]
Check against a reliable thermometer.
Adjust per instructions with thermostat ........... [ ]
(Indoor blower motor) ..................................... [ ]
to insure safe operation. ................................. [ ]
From Dwg. 21D152989 Rev. 0
Pub. No. 11-AC24D1-1
7/07